Operation 

26MXXXXX-XX-XX 

AUTOMATIC  RESET  (Reset  Switch  terminals  not  wired) 
When the liquid rises to the electrode on terminal LLCO, the 
control energizes, changing state of the load contacts. (LED 
will  be  lit)  The  control  remains  energized  until  the  liquid 
level recedes below electrode on terminal LLCO. The con-
trol  then  de-energizes,  (LED  will  not  be  lit)  returning  load 
contacts to original state. Unless otherwise specified, there 
is  a  three  second  time  delay  on  decreasing  level.  Liquid 
must be below probe on terminal LLCO for a full three sec-
onds before control de-energizes.  

MANUAL  RESET  (Normally  closed  pushbutton  installed 
across  reset  terminals)  When  the  liquid  rises  to  the  elec-
trode  on  terminal  LLCO,  the  control  will  remain  de-
energized  until  the  pushbutton  is  depressed.  Upon  Reset 
Switch activation, the control will energize, (LED will be lit) 
changing  the  state  of  the  contacts.  The  control  remains 
energized until  the  liquid  level  recedes below  electrode  on 
terminal LLCO. The control then de-energizes, (LED will not 
be lit) returning load contacts to their original state. Unless 
otherwise  specified,  there  is  a  three  second  time  delay  on 
decreasing  level.  Liquid  must  be  below  probe  on  terminal 
LLCO  for  full  three  seconds  before  control  de-energizes. 
Operator to wait 5 full seconds after power is applied before 
pressing reset switch (if manual reset is used). 

MANUAL RESET OPTIONAL POWER OUTAGE FEA-
TURE (Normally closed pushbutton across reset terminals) 
Control will auto-recover from a power loss. With liquid pre-
sent on LLCO electrode at a power outage event, the con-
trol will de-energize and will automatically re-energize upon 
return of power with liquid present on the probe at power-
up. However, if loss of liquid is sensed on power-up, the 
control will remain de-energized until liquid again rises to 
electrode and pushbutton is depressed. The control will not 
attempt to auto-recover from a power outage if no liquid 
was present on the probe at power loss. 

 

TEST FEATURE  

Allows  LLCO  circuit  to  be  tested  without  the  need  to  drop 
the water level in the boiler to create a dry probe condition. 
Holding  down  the  reset  button  for  3 seconds  will  allow  the 
LLCO  circuit  to  trip,  simulating  a  dry  probe.  The  controller 
will  return  to  normal  operation  once  the  reset  button  is 
pressed a second time. 

LED  STATUS  INDICATOR  In  normal  operation,  the  LED 
on  the  control  will  either  be  on  or  off  depending  on  the 
controller  state.  On-board  microprocessors  continuously 
monitor for fault conditions. In the event a fault is detected, 
the LED will blink a pattern indicating the fault type. If you 
experience an inoperable control and the LED is blinking, 
attempt to leave the control in the blinking state and con-
tact the factory for assistance.

 

Time Delay Increasing Level: 0-90 
seconds, Blank = 0 seconds. 
Time Delay Decreasing Level: 0-90 
seconds, Blank = 3 seconds. 
Optional Character: see Chart  
Enclosure: 0-None, 1-NEMA 1, 2-
NEMA 4 

Socket Style: A-11 Pin Octal, B-Din 
Mount, M-NONE, Module Only  

Supply Voltage: 1-120VAC (+10%/
-15%), 2-240VAC (+10%/-15%), 3-
24VAC (+10%/-15%), 5-220VAC 
(+10%/-15%), 8-208/240VAC (187 
to 242 VAC absolute Range)  
Mode/Sensitivity: A-4.7K, B-10K, 
C-26K, D-50K, E-100K  

  

N.C. 

Pushbutton 

Power 

Outage 

Test    

Feature 

 

 

  

  

  

  

  

X  

 

 

No Option     

Wiring Diagram 