ELECTRICAL CONNECTIONS

Connection of 3-phase load and 2-phase control 

Connection of single-phase load 

Heatsink (accessory)

Connection of 3-phase load with closed/open triangle or star

Digital
output
on/off

Relay
output

spread 1 gram of thermoconductive sili-

cone paste (we recommend DOW COR-

NING 340) on the dissipative metal surfa-

ces of the module.

The surfaces must be clean and the ther-

moconductive paste must not contain

any impurities. As alternative it is also

possible to use the slide SIL-GQ availa-

ble as accessory.

Alternately tighten the two fastening

screws until reaching a torque of

0.4…0.6 Nm.

Wait 5 minutes for any excess paste to

run off.

Alternately tighten the two fastening

screws until reaching a torque of

1.2…1.4 Nm.

Attention

The contact surface of the heatsink

module may have a maximum planarity

error of 0.1 mm and maximum roughness

of 0.02 mm.

The fastening holes on the heatsink must

be threaded and countersunk.

The heatsink must be grounded.