81901A “MSW_GPC-40/600A”_03-2021_ENG_page 85
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
The parameter sets the allocation of the value of another parameter, or a function of parameters, to the reference signal
rL.x
, with x rang-
ing from 1 to 6. The reference signal must be understood as an internal status.
To associate an alarm with an output, first associate the alarm with a
rL.x
reference signal, then associate the same
rL.x
reference signal
with an output.
The signal allocation is identified by an index.
Options:
Index
Parameter or function
0
Ou.P
(control output) *
2
AL1
(alarm 1)
3
AL2
(alarm 2)
4
AL3
(alarm 3)
5
AL.HB
OR
POWER_FAULT
with
HB
alarm (
TA1
OR
TA2
OR
TA3
)
7
IN1
(INDIG1 logic input repetition)
8
AL4
(alarm 4)
9
AL1
OR
AL2
10
AL1
OR
AL2
OR
AL3
11
AL1
OR
AL2
OR
AL3
OR
AL4
12
AL1
AND
AL2
13
AL1
AND
AL2
AND
AL3
14
AL1
AND
AL2
AND
AL3
AND
AL4
15
AL1
OR
AL.HB
OR
POWER_FAULT
with
HB
alarm (
TA1
OR
TA2
OR
TA3
)
16
AL1
OR
AL2
OR (
AL.HB
OR
POWER_FAULT
) with
HB
alarm (
TA1
OR
TA2
OR
TA3
)
17
AL1
AND (
AL.HB
OR
POWER_FAULT
) with
HB
alarm (
TA1
OR
TA2
OR
TA3
)
18
AL1
AND
AL2
OR (
AL.HB
OR
POWER_ FAULT
) with
HB
alarm (
TA1
OR
TA2
OR
TA3
)
19
AL.HB
(HB alarm
TA2
)
20
AL.HB
(HB alarm
TA3
)
22
AL.HB
(alarm
HB TA1
)
23
POWER_FAULT
(
SSR_SHORT
OR
NO_VOLTAGE
OR
NO_CURRENT
)
24
IN2
(INDIG2 logic input repetition)
25
IN3
(INDIG3 logic input repetition)
26
IN4
(INDIG4 logic input repetition)
27
FUSE_OPEN
/
SHORT_CIRCUIT_CURRENT
28
Overtemperature alarm
29
Communication error
30
Device not ready (
DEVICE_NOT_READY
)
64
Ou.P
(control output) with fast cycle time 0.1...20.0 seconds *
Notes
:
*) only for
rL.1
and
rL.2
.
OR and AND are to be understood as Boolean operators and determine the result of the function.
AL1
OR
AL2
OR
AL3
, for example, pro-
vides TRUE if at least one of the three alarms is active;
AL1
AND
AL2
AND
AL3
, for example, only provides TRUE if all alarms are active.
Increasing the index by a fixed amount results in the following behaviours:
Index +32
= The output logic level is negated (if TRUE becomes FALSE and vice versa).
Index +128 = Output is forced to 0.