81901A “MSW_GPC-40/600A”_03-2021_ENG_page 115
3.30.5.
Firing Change status set via serial
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1921
897
16 bit
SERI-
AL_FC
M
MainMenu
→
M
→
Expert
→
Virtual
→
SERIAL_FC_1
R/W
Unsigned
Short
0
2945
E1
MainMenu
→
M
→
Expert
→
Virtual
→
SERIAL_FC_2
4993
E2
MainMenu
→
M
→
Expert
→
Virtual
→
SERIAL_FC_3
The parameter sets the Firing Change mode set via serial.
Options:
0
= ZC/BF/HSC mode
1
= PA mode
3.30.6.
Firing Change status set via serial
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1145
121
bit
BIT_
SERIAL_
FC_PA_
MODE
M
MainMenu
→
M
→
Expert
→
Bit
→
BIT_SERIAL_FC_PA_MODE_1
R/W
OFF
2169
E1
MainMenu
→
E1
→
Expert
→
Bit
→
BIT_SERIAL_FC_PA_MODE_2
4217
E2
MainMenu
→
E2
→
Expert
→
Bit
→
BIT_SERIAL_FC_PA_MODE_3
The bit sets the Firing Change mode set via serial.
Options:
OFF
= ZC/BF/HSC mode
ON
= PA mode