81901 “MSW_GPC-40/600A”_03-2021_ENG_page 102
3.22.3.
Status (STATUS_W)
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1329
305
16 bit
07.02.14
STA-
TUS_W
M
MainMenu
→
M
→
Controls
→
STATUS_W_1
R/W
■
Unsigned
Short
0
2353
07.03.14
E1
MainMenu
→
E1
→
Controls
→
STATUS_W_2
4401
01.04.14
E2
MainMenu
→
E2
→
Controls
→
STATUS_W_3
The parameter sets the Automatic/Manual and Software startup/shutdown operating status of the controller with bits.
Options
:
bit
Status setting
3
ON/OFF selection
4
AUTO/MAN selection
3.23. Manual power correction
In manual operation, the power output can be corrected
automatically in relation to the reference mains voltage (
riF
).
The
% correction value (
Cor
) is freely adjustable and acts in
an inversely proportional manner, i.e., if the reference volt-
age increases, the power output decreases, and vice versa
.
The function is switched on and off via the
SP.r
parameter.
In addition to the parameters explained below, the STA-
TUS_W parameter should also be considered in manual
power correction (see paragraph “3.22.3. Status (STA-
TUS_W)”.
When moving from AUTO to MAN mode, sudden output
changes are possible.
3.23.1.
Mains voltage
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1529
505
16 bit
07.02.07
riF
M
MainMenu
→
M
→
Controls
→
riF_1
R/W
■
Float
(####.#)
V
0.0
2553
07.03.07
E1
MainMenu
→
M
→
Controls
→
riF_2
4601
01.04.07
E2
MainMenu
→
M
→
Controls
→
riF_3
The parameter sets the reference mains voltage, i.e., the voltage value against which the actual voltage is compared in order to keep the
output power constant.
min...max:
0.0
...
999.9
3.23.2.
Manual power correction
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1530
506
16 bit
07.02.08
Cor
M
MainMenu
→
M
→
Controls
→
Cor_1
R/W
■
Float
(####.#)
%
0.0
2554
07.03.08
E1
MainMenu
→
E1
→
Controls
→
Cor_2
4602
01.04.08
E2
MainMenu
→
E2
→
Controls
→
Cor_3
The parameter sets the manual power correction depending on the mains voltage.
The maximum manual power correction is limited to ± 65%.
min...max:
0.0
...
100.0