81901A “MSW_GPC-40/600A”_03-2021_ENG_page 41
3.12.5.
PWM input timeout
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1380
356
16 bit
04:17:09
PWm.t1
Global
MainMenu
→
Global
→
Inputs
→
Digital inputs
→
PWm.t1
R/W
■
Float
(####.#)
sec.
0.01
1381
357
16 bit
04:17:10
PWm.t2
Global
MainMenu
→
Global
→
Inputs
→
Digital inputs
→
PWm.t2
R/W
■
Float
(####.#)
sec.
1.00
1386
362
16 bit
04:17:11
PWm.t3
Global
MainMenu
→
Global
→
Inputs
→
Digital inputs
→
PWm.t3
R/W
■
Float
(####.#)
sec.
1.00
The parameter sets the timeout for the digital input PWM 1, PWM 2 or PWM 3, depending on the address used.
IMPORTANT!
If the digital input is used to control the power percentage (parameter
Ou.P
) to be delivered on the load (PWM input func-
tion,
dIG
= 7), the parameter
PWm.t
must be set to a value equal to or greater than the period of the PWM control signal used, in order to
guarantee the reaction time even in static conditions of low (
Ou.P
= 0%) or high (
Ou.P
= 100%) input.
min...max
:
0.01
..
.
10.00
3.12.6.
Digital filter for PWM input
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1462
438
16 bit
04:17:06
Ft.PWm1
Global
MainMenu
→
Global
→
Inputs
→
Digital inputs
→
Ft.PWm1
R/W
■
Float
(####.#)
sec.
0.1
1396
372
16 bit
04:17:07
Ft.PWm2
Global
MainMenu
→
Global
→
Inputs
→
Digital inputs
→
Ft.PWm2
R/W
■
Float
(####.#)
sec.
0.1
1397
373
16 bit
04:17:08
Ft.PWm3
Global
MainMenu
→
Global
→
Inputs
→
Digital inputs
→
Ft.PWm3
R/W
■
Float
(####.#)
sec.
0.1
This parameter sets the value of the digital filter time constant applied to the value read from digital input PWM 1, PWM 2 or PWM 3,
depending on the address used. The filter calculates the average of the values read in the specified time interval.
With 0.0 no filter is applied.
min...max
:
0.0
...
20.0
3.12.7.
PWM input value
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1542
518
16 bit
04.01.04
In.Pwm1
Global MainMenu
→
Global
→
Status
→
In.Pwm1
R
Float
(####.#)
%
1459
435
16 bit
04.01.05
In.Pwm2
Global MainMenu
→
Global
→
Status
→
In.Pwm2
R
Float
(####.#)
%
1481
457
16 bit
04.01.06
In.Pwm3
Global MainMenu
→
Global
→
Status
→
In.Pwm3
R
Float
(####.#)
%
The parameter shows the value of the input PWM 1, PWM 2 or PWM 3, depending on the address used, as a percentage of the ON state
compared to the ON + OFF period.
min...max
:
0.0
...
100.0