72
80963B_MSW_GFW_11-2012_ENG
633
R
State 3 (STATUS3)
Table of state 3
634
R
State 4 (STATUS4)
Table of state 4
702
R
Voltage status
Table of voltage status
Functionality key
bit
0
Temperature sensor broken
1
over heat
2 phase_softstart_active
3 phase_softstart_end
4
frequency_warning or monophase_missing_line_warning
5 60Hz
6
short_circuit_current in softstart di fase
7
over_peak_current in softstart di fase
8
over_rms_current a regime
9
SSR_Safety (24V fan presence or SSR hardware over temperature)
10
Fuse open
11
Current polarity check
12
over_peak_current_projection in softstart di fase
bit
0
frequency_warning
1
10% unbalanced_line_warning
2
20% unbalanced_line_warning
3
30% unbalanced_line_warning
4 rotation123_error
5 three-phase_missing_line_error
6 60Hz
bit
3
AL.SSR short 1
4
AL.SSR short 2
5
AL.SSR short 3
6
No voltage 1
7
No voltage 2
8
No Voltage 3
9
No current 1
10
No current 2
11
No current 3
(*) with key pressed, the state of the RN and
BUT
LEDs is steadily on; the
LEDs switch off after 2/3 seconds to indicate switching to ready state.
Example:
To activate calibration of the HB alarm, keep the key pressed for 3 seconds,
release the key and then press it again for another 3 seconds.
LED RN
(green) flashing
LED BUT
(yellow) off
Key
pressed
> 3 sec (*)
Key
pressed
> 3 sec (*)
Key
pressed
> 3 sec (*)
Key pressed
> 1 sec (*)
Key pressed
> 1 sec (*)
Normal
operation
LED RN
(green) steadily on
LED BUT
(yellow) 1 flash
every second.
Ready for
calibration HB alarm
LED RN
(green) flashing
rapidly
LED BUT
(yellow) flashing
rapidly
Calibration HB alarm
LED RN
(green) flashing
rapidly
LED BUT
(yellow) flashing
rapidly
Reset PF alarms
with latch
LED RN
(green) steadily on
LED BUT
(yellow) 2 flashes
every second
Presetting for reset
PF alarms with latch
LED RN
(green) off
LED BUT
(yellow) off
Reset FUSE_OPEN/SHORT_
CIRCUIT_CURRENT alarms
Monophase configuration
LED RN
(green) flashing
LED ER
(red) flashing
LED BUT
(yellow) off
3-phase configuration
All LEDs flash rapidly except for
LED BUT
(yellow) FUSE_OPEN alarm
or
LED 01
(yellow) SHORT_CIRCUIT_CURRENT alarm
FUSE_OPEN /
SHORT_CIRCUIT_CURRENT alarms
Key
pressed
> 2 sec (*)