
39
80963B_MSW_GFW_11-2012_ENG
SBR - ERR ALARM
(probe in short or connection error)
This alarm is always ON and cannot be deactivated. It controls correct functioning of the probe connected to the main
input.
In case of broken probe:
- the state of alarms AL1, AL2, AL3 and AL4 is set based on the value of parameter rEL;
- control power control is set to the value of parameter FAP.
Identification of the type of break detected on the main input is contained in Err.
9
bit
STATE OF INPUT
IN SBR
OFF = -
ON = Input in SBR
R
Enable alarm
229
rEL
R/W
Fault action
(definition of state in case
of broken probe)
Sbr, Err
Only for main input
0
Alarm
Alarm
Alarm
Alarm
1
2
3
4
0
OFF
OFF
OFF
OFF
1
ON
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
3
ON
ON
OFF
OFF
4
OFF
OFF
ON
OFF
5
ON
OFF
ON
OFF
6
OFF
ON
ON
OFF
7
ON
ON
ON
OFF
8
OFF
OFF
OFF
ON
9
ON
OFF
OFF
ON
10
OFF
ON
OFF
ON
11
ON
ON
OFF
ON
12
OFF
OFF
ON
ON
13
ON
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON
Table of probe alarm settings
228
fa.p
R/W
Fault action power
(supplied in conditions of broken probe)
-100,0 ..100,0 %
0,0
see: OTHER FUNCTION
Read state
85
Err
R
Error code in self-diagnostics
of main input
See: Table of error codes
Содержание GFW ADV
Страница 2: ...2 80963B_MSW_GFW_11 2012_ENG ...