R/W
Control type
134
Table of heat/cool controls
Select sample time for derivative action.
+0 sample 1 sec.
+16 sample 4 sec.
+32 sample 8 sec.
+64 sample 240 msec.
+128 No Reset of integral component at setpoint change
Note: the LBA alarm is not enabled in the ON/OFF control.
Val
Control type
0
P heat
1
P cool
2
P heat / cool
3
PI heat
4
PI cool
5
PI heat / cool
6
PID heat
7
PID cool
8
PID heat / cool
9
ON-OFF heat
10
ON-OFF cool
11
ON-OFF heat / cool
12
PID heat + ON-OFF cool
13
ON-OFF heat + PID cool
14
PID heat + cool with relative gain (see parameter C.MEd)
PID Parameters
617*
spu
R/W
Reference power
Table of selections
- The reference power of a slave zone in automatic mode is the power of a master
zone in automatic or manual mode.
- The reference power of a slave zone in manual mode is the zone manual power.
- Software shutdown remains independent for each zone.
0
zone1
0
zone2
0
zone3
(**) function “slave” zone
SPU
0
Power from analog input (In.A)
1
Power from main input (PV)
2
Power from aux input (In.2)
3
Power from aux input (In.3)
4
Power from aux input (In.4)
5
Power from aux input (In.5)
6
Power from PID (PID_POWER) (**)
7
Power from digital input (In.Pwm)
9
Power from GFW-M (FW_POWER) (**)
10
Power from GFW-E1 (FW_POWER) (**)
11
Power from GFW-E2 (FW_POWER) (**)
513
R/W
Select cooling fluid
0 ...2
0
Relative gain (rG)
0
Air
1
1
Oil
0,8
2
Water
0,4
77
c.dt
R/W
Derivative cooling time
0.00 ...99,99 min
1,00
Note: Parameters c.PB, c.It and c.dt are read-only if heat/cool control is enabled with relative gain (Ctr = 14).
6
c.pb
R/W
Proportional band
for cooling or hyste-
resis ON/OFF
0 ...999,9% f.s.
1,0
76
c.1t
R/W
Integral cooling time
0.00 ...99,99 min
4,00
2*
132 - 471
0v.p
R
Value of control outputs
(+Heat / -Cool)
(W – only in manual mode at address 252)
Read state
5
148 - 149
h.pb
R/W
Proportional band
for heating or hyste-
resis ON/OFF
0 ...999,9% f.s.
1,0
7
150
h.1t
R/W
Integral heating time
0.00 ...99,99 min
4,00
8
151
h.dt
R/W
Derivative heating time
0.00 ...99,99 min
1,00
(.Ae