18Vdc, 50mA
for 2-wire transmitter

2 4

Static D2

D 0

1.2Vdc for potentiometer (*)

0 1

Power supply

27Vdc, 18...27Vac not isolated

9

Output 3

Absent

0 0

Relay

R 0

Sensor power supply

None

0 0

For T input (alternative to RTD, PTC)

Output 1, Output 2

Relay, Relay

R R

Relay, Static D2

Triac, None

R D

T 0

• WARNINGS

ORDER CODE 

40T

Read the following warnings before installing, connecting or using the device:
• follow instructions precisely when connecting the device.
• always use cables that are suitable for the voltage and current levels indicated in the technical specifications.
• the device has no ON/OFF switch: it switches on immediately when power is turned on. For safety reasons, devices permanently connected to the power
supply require a two-phase disconnecting switch with proper marking. Such switch must be located near the device and must be easily reachable by the
user. A single switch can control several units.
• if the device is connected to electrically NON-ISOLATED equipment (e.g. thermocouples), a grounding wire must be applied to assure that this
connection is not made directly through the machine structure.
• if the device is used in applications where there is risk of injury to persons and/or damage to machines or materials, it MUST be used with auxiliary alarm
units. You should be able to check the correct operation of such units during normal operation of the device. 
• before using the device, the user must check that all device parameters are correctly set in order to avoid injury to persons and/or damage to property.
• the device must NOT be used in inflammable or explosive environments. It may be connected to units operating in such environments only by means of
suitable interfaces in conformity to local safety regulations.
• the device contains components that are sensitive to static electrical discharges. Therefore, take appropriate precautions when handling electronic circuit
boards in order to prevent permanent damage to these components.
Installationinstallation category II, pollution level 2, double isolation
• power supply lines must be separated from device input and output lines; always check that the supply voltage matches the voltage indicated on the
device label.
• install the instrumentation separately from the relays and power switching devices
• do not install high-power remote switches, contactors, relays, thyristor power units (particularly if “phase angle” type), motors, etc... in the same cabinet.
• avoid dust, humidity, corrosive gases and heat sources.
• do not close the ventilation holes; working temperature must be in the range of 0...50°C.
If the device has faston terminals, they must be protected and isolated; if the device has screw terminals, wires should be attached at least in pairs.
• Power: supplied from a disconnecting switch with fuse for the device section; path of wires from switch to devices should be as straight as possible; the
same supply should not be used to power relays, contactors, solenoid valves, etc.; if the voltage waveform is strongly distorted by thyristor switching units
or by electric motors, it is recommended that an isolation transformer be used only for the devices, connecting the screen to ground; it is important for the
electrical system to have a good ground connection; voltage between neutral and ground must not exceed 1V and resistance must be less than 6Ohm; if
the supply voltage is highly variable, use a voltage stabilizer for the device; use line filters in the vicinity of high frequency generators or arc welders;
power supply lines must be separated from device input and output lines; always check that the supply voltage matches the voltage indicated on the
device label.
• Input and output connections: external connected circuits must have double insulation; to connect analog inputs (TC, RTD) you have to: physically
separate input wiring from power supply wiring, from output wiring, and from power connections; use twisted and screened cables, with screen connected
to ground at only one point; to connect adjustment and alarm outputs (contactors, solenoid valves, motors, fans, etc.), install RC groups (resistor and
capacitor in series) in parallel with inductive loads that work in AC (Note: all capacitors must conform to VDE standards (class x2) and support at least 220
VAC. Resistors must be at least 2W)
; fit a 1N4007 diode in parallel with the coil of inductive loads that operate in DC.
GEFRAN spa will not be held liable for any injury to persons and/or damage to property deriving from tampering, from any incorrect or
erroneous use, or from any use not conforming to the device specifications.

!

WARNING: this symbol indicates danger.
It is seen near the power supply circuit and near high-voltage relay contacts.

17

72

9

PID

Kindly contact GEFRAN for information on available codes.

(*) For input from potentiometer, request version P77 (R input > 10M

)

Содержание 40T 72 PID

Страница 1: ...pply option 18V 10 50mA 1 2V for potentiometer 100 Ω version P77 Power supply not isolated from sensor input 11 27Vdc 18 27Vac 10 50 60Hz 4 5VA Display 4 digit red LED s digit height 14mm Keys 3 mechanical keys Raise Lower F Accuracy 0 2 f s at 25 C ambient temperature 76 72 36 30 69 5 43 83 52 9 5 1 INSTALLATION Dimensions and cut out Panel mounting Panel mounting Fix the device with the bracket ...

Страница 2: ...IPTION OF FACEPLATE Function key Gives access to different configuration stages Confirms any parameter changes Standard 18 to 27 Vac 11 to 27Vdc 10 50 60 Hz 4 5 VA max not isolated from sensor input Linear Input V Outputs Pt100 PTC NTC 3 1 2 2 1 Linear Input I 4 1 2 10 8 9 7 Out1 Out2 Power supply 11 12 Outputs TC 2 1 4 2 3 1 Ri 50Ω 4 20mA Linear input with 2 wire transmitter PWR PV display Indica...

Страница 3: ...u 5 Standard Configuration Menu Enable selftuning autotuning softstart Proportional band for heating or hysteresis in regulation ON OFF Integral heating time Derived heating time Maximum limit heating power S tu Autotuning Selftuning Softstart continuous 0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 0 999 9 f s 0 00 99 99 min 0 00 99 99 min 0 0 100 0 0 10 0 4 0 1 0 100 0 Default Cust...

Страница 4: ...min Reset power 100 0 100 0 999 scale points Hysteresis for alarm 2 Hysteresis for alarm 1 999 scale points Hysteresis for alarm 3 Integral cooling time 0 00 99 99 min Derived cooling time 0 00 99 99 min Manual reset 999 999 scale points Maximum limit cooling power 0 0 100 0 N B the LBA alarm is excluded for ON OFF controls 13 6 PROGRAMMING and CONFIGURATION F If the Inc Dec F keys are not pressed...

Страница 5: ...YP Signal type Scale Max scale range 24 0 10V linear 1999 9999 25 2 10V linear 1999 9999 SENSOR VOLTAGE 10V or TRANSMITTER CAL 6 InP Input settings Digital filter on main input Digital filter on display of process variable acts as hysteresis Decimal point position for main input scale not available for TC RTD PTC scales Minimum limit of main input scale Maximum limit of main input scale Main input...

Страница 6: ...ycle time OUT3 relay or logic HEAT or COOL 0 200 sec Prot Pro Protection code Pro Display Change 0 SP alarms OutP SP alarms 1 SP alarms OutP SP 2 SP SP 3 SP 4 disable InP Out 8 disable CFG 16 disable SW turn on turn off To activate the turn off SW function press keys F for 5 secs in P V To return to normal functioning press key F for 5 secs 15 OUT 1 Attribution of reference signal HEAT COOL AL1 AL...

Страница 7: ...by means of the TRAFO1 transformers specified in the manual one for each device when The application is unknown Multiple devices have input signals that are not isolated from one another such as for example non isolated grounded thermocouples transducers or transmitters powered by a single supply linear inputs with voltage or current not isolated from one another It is a general rule that devices ...

Страница 8: ... remote switches contactors relays thyristor power units particularly if phase angle type motors etc in the same cabinet avoid dust humidity corrosive gases and heat sources do not close the ventilation holes working temperature must be in the range of 0 50 C If the device has faston terminals they must be protected and isolated if the device has screw terminals wires should be attached at least i...

Отзывы: