gefran 40T 72 PID Скачать руководство пользователя страница 2

Generic user-

configurable outputs

- relay 5A/250Vac
- logic 6V/20mA,

Rout = 560

with power supply
> 18Vac/dc

- Triac 20...240Vac 

±10%, 2Amax

• Linear input for potentiometer

11

Generic user-

configurable output

- relay 5A/250Vac

Out3

5

6

Available thermocouples:

J, K, R, S, T, B, E, N

- Respect polarities
- For extensions, use
compensated cable
appropriate for
thermocouple.

Use wires of adequate

thickness (min. 1mm

2

)

PT100, JPT100,

PTC

dc current

linear input

20mA, Ri = 50

(The signal must be

insulated from power

supply)

dc voltage linear input

60mV, 1V, 5V, 10V,

Ri 

500K

(The signal must be

insulated from power

supply.)

“Raise” and “Lower” keys:

These keys are used for any operation that
requires a numerical parameter to be raised or
lowered. ••The speed of change is proportional to
the time the key is pressed. •• The operation is
not cyclic: once the maximum (minimum) limit is
reached, there will be no further increase
(decrease) of the value, even if the key remains
pressed.

3 • DESCRIPTION OF FACEPLATE

Function key:

Gives access to different configuration stages ••
Confirms any parameter changes

Standard:

18 to 27 Vac, 11 to 27Vdc

±10%

50/60 Hz, 4.5 VA max. not

isolated from sensor input

• Linear Input (V)  

• Outputs

• Pt100 / PTC / NTC

3

1

2

2

1

+

-

• Linear Input (I) 

4

1

2

-

+

10

8

9

7

+

-

Out1

+

-

Out2

• Power supply

11

12

~

~

• Outputs

+

-

• TC 

2

1

4

2

3

1

+

-

+

-

Ri = 50

4...20mA

• Linear input with 2-wire transmitter

PWR

PV display: Indication of process variable ••
Indication of ‘HI’ or ‘Lo’ out of range •• Indication of
open circuit (br) or short circuit (Er) •• Display of
configuration and calibration messages

Indication of output states:

OUT 1 (MAIN); OUT 2 (Alarm 1); OUT 3 (Alarm 2)

12

4

11

3

2

1

5

6

9

10

8

7

!

Label with engineering units

4 • CONNECTIONS

3-wire Pt100

2-wire PTC

Pt100

T

T

4

2

3

1

Potentiometer

R >100

+  1,2Vdc

-

• Inputs

~

~

Line

Load

Rin
>10M
(P77)

• Device structure: identification of boards

S3

S4

CPU board

OUTPUT board

RTD, PTC, NTC

input

ON

OFF

Transmitter and

potentiometer
power supply

OFF

ON

S3

S4

S9

S8

S5

S1

S4

S6

S3

S7

Voltage

1V

24V (18V)

Jumpers

S4 - S6B - S7A

S6B - S7A

Probe power supply

S5 = Status of Out 1 relay
S8 = Status of Out 2 relay
S9 = Status of Out 2 relay
A = Direct
B = Inverse

Содержание 40T 72 PID

Страница 1: ...pply option 18V 10 50mA 1 2V for potentiometer 100 Ω version P77 Power supply not isolated from sensor input 11 27Vdc 18 27Vac 10 50 60Hz 4 5VA Display 4 digit red LED s digit height 14mm Keys 3 mechanical keys Raise Lower F Accuracy 0 2 f s at 25 C ambient temperature 76 72 36 30 69 5 43 83 52 9 5 1 INSTALLATION Dimensions and cut out Panel mounting Panel mounting Fix the device with the bracket ...

Страница 2: ...IPTION OF FACEPLATE Function key Gives access to different configuration stages Confirms any parameter changes Standard 18 to 27 Vac 11 to 27Vdc 10 50 60 Hz 4 5 VA max not isolated from sensor input Linear Input V Outputs Pt100 PTC NTC 3 1 2 2 1 Linear Input I 4 1 2 10 8 9 7 Out1 Out2 Power supply 11 12 Outputs TC 2 1 4 2 3 1 Ri 50Ω 4 20mA Linear input with 2 wire transmitter PWR PV display Indica...

Страница 3: ...u 5 Standard Configuration Menu Enable selftuning autotuning softstart Proportional band for heating or hysteresis in regulation ON OFF Integral heating time Derived heating time Maximum limit heating power S tu Autotuning Selftuning Softstart continuous 0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 0 999 9 f s 0 00 99 99 min 0 00 99 99 min 0 0 100 0 0 10 0 4 0 1 0 100 0 Default Cust...

Страница 4: ...min Reset power 100 0 100 0 999 scale points Hysteresis for alarm 2 Hysteresis for alarm 1 999 scale points Hysteresis for alarm 3 Integral cooling time 0 00 99 99 min Derived cooling time 0 00 99 99 min Manual reset 999 999 scale points Maximum limit cooling power 0 0 100 0 N B the LBA alarm is excluded for ON OFF controls 13 6 PROGRAMMING and CONFIGURATION F If the Inc Dec F keys are not pressed...

Страница 5: ...YP Signal type Scale Max scale range 24 0 10V linear 1999 9999 25 2 10V linear 1999 9999 SENSOR VOLTAGE 10V or TRANSMITTER CAL 6 InP Input settings Digital filter on main input Digital filter on display of process variable acts as hysteresis Decimal point position for main input scale not available for TC RTD PTC scales Minimum limit of main input scale Maximum limit of main input scale Main input...

Страница 6: ...ycle time OUT3 relay or logic HEAT or COOL 0 200 sec Prot Pro Protection code Pro Display Change 0 SP alarms OutP SP alarms 1 SP alarms OutP SP 2 SP SP 3 SP 4 disable InP Out 8 disable CFG 16 disable SW turn on turn off To activate the turn off SW function press keys F for 5 secs in P V To return to normal functioning press key F for 5 secs 15 OUT 1 Attribution of reference signal HEAT COOL AL1 AL...

Страница 7: ...by means of the TRAFO1 transformers specified in the manual one for each device when The application is unknown Multiple devices have input signals that are not isolated from one another such as for example non isolated grounded thermocouples transducers or transmitters powered by a single supply linear inputs with voltage or current not isolated from one another It is a general rule that devices ...

Страница 8: ... remote switches contactors relays thyristor power units particularly if phase angle type motors etc in the same cabinet avoid dust humidity corrosive gases and heat sources do not close the ventilation holes working temperature must be in the range of 0 50 C If the device has faston terminals they must be protected and isolated if the device has screw terminals wires should be attached at least i...

Отзывы: