gefran 40T 72 PID Скачать руководство пользователя страница 5

• Out

• InP  

Lo.S ... Hi.S

Type of probe, signal and scale of main input

tYP Type of probe

Scale

Max. scale range

Max. scale range

(C/F)

without decimal point

with decimal point

0

J (Fe-CuNi)

C

0 / 1000

0,0 / 999,9

1

J (Fe-CuNi)

F

32 / 1832

32,0 / 999,9

2

K (NiCr-Ni)

C

0 / 1300

0,0 / 999,9

3

K (NiCr-Ni)

F

32 / 2372

32,0 / 999,9

4

R (Pt13Rh - Pt)

C

0 / 1750

not available

5

R (Pt13Rh - Pt)

F

32 / 3182

not available

6

S (Pt10Rh - Pt)

C

0 / 1750

not available

7

S (Pt10Rh - Pt)

F

32 / 3182

not available

8

T (Cu-CuNi)

C

-200 / 400

-199,9 / 400,0

9

T (Cu-CuNi)

F

-328 / 752

-199,9 / 752,0

10

B (Pt30Rh - Pt6Rh)

C

44 / 1800

not available

11

B (Pt30Rh - Pt6Rh)

F

111 / 3272

not available

12

E (NiCr-CuNi)

C

-100 / 750

-100,0 / 750,0

13

E (NiCr-CuNi)

F

-148 / 1382

-148,0 / 999,9

14

N (NiCrSi-NiSi)

C

0 / 1300

0,0 / 999,9

15

N (NiCrSi-NiSi)

F

32 / 2372

32,0 / 999,9

tYP

Type of probe

Scale

Max. scale range

Max. scale range

(C/F)

without decimal point

with decimal point

16

PT100

C

-200 / 600

-199,9 / 600,0

17

PT100

F

-328 / 1112

-199,9 / 999,9

SENSOR: RTD 3 wires

(CAL = 2)

tYP

Type of probe

Scale

Max. scale range

Max. scale range

(C/F)

without decimal point

with decimal point

18

PTC

C

-55 / 120

-55.0 / 120.0

19

PTC

F

-67 / 248

-67.0 / 248.0

SENSOR: PTC (on request) [alternate to RTD 3 wires]

(CAL = 3)

tYP

Signal type

Scale

Max. scale range

20

0...60mV

linear

-1999 / 9999 

21

12...60mV

linear

-1999 / 9999

SENSOR: VOLTAGE 60Mv

(CAL = 4)

tYP

Signal type

Scale

Max. scale range

22

0...20mA

linear

-1999 / 9999

23

4...20mA

linear

-1999 / 9999

SENSOR: CURRENT 20mA or TRANSMITTER

(CAL = 5)

tYP

Signal type

Scale

Max. scale range

24

0...10V

linear

-1999 / 9999

25

2...10V

linear

-1999 / 9999

SENSOR: VOLTAGE 10V or TRANSMITTER

(CAL = 6)

InP 

Input settings

Digital filter

on main input

Digital filter on display of

process variable; acts as

hysteresis

Decimal point position for

main input scale

(*) not available for
TC, RTD, PTC scales

Minimum limit of main

input scale

Maximum limit of main

input scale

Main input offset

correction

Lower limit for local setpoint

and absolute alarms

SENSOR: TC

(CAL = 1)

0.0 to 20.0 sec

0.0 to 9.9

scale points

dP.S

Format

0

xxxx

1

xxx.x

2

xx.xx (*)

3

x.xxx (*)

min…max scale of input

selected in t.P

min…max scale of input

selected in t.P

-999…999

scale points

Lo.S ... Hi.S

Upper limit for local setpoint

and absolute alarms

Type of control

[0...27]

CtrL

Type of control

0

P heat

1

P cool

2

P heat / cool

3

PI heat

4

PI cool

5

PI heat / cool

6

PID heat

7

PID cool

8

PID heat / cool

9

ON-OFF heat

10

ON-OFF cool

11

ON-OFF heat / cool

0

0

0

1000

22

Default   Custom

Configurat.

Out 

Output settings

to disable on power-up until first alarm

AL.x

Direct

Absolute

Normal

(max.)

Relative

Symmetrical

Inverse

to previous

(window)

(min.)

0

direct

absolute

normal

1

inverse

absolute

normal

2

direct

relativo

normal

3

inverse

relativo

normal

4

direct

absolute

symmetrical

5

inverse

absolute

symmetrical

6

direct

relativo

symmetrical

7

inverse

relativo

symmetrical

0 ... 3

Number of alarms

Alarm

type 1

Alarm

type 2

Alarm

type 3

Default   Custom

Configurat.

0

+16 disable parameters

CFGrst, PrE, SoF, Lbt, Lbp, FAP,

HY.2, HY.3

InPFLt, FLd, oFS, LoL, HIL
OutALn, A2t, A3t, rEL.

FLt, FLd, oFS stay at set value.
All other parameters are considered 0.

14

Содержание 40T 72 PID

Страница 1: ...pply option 18V 10 50mA 1 2V for potentiometer 100 Ω version P77 Power supply not isolated from sensor input 11 27Vdc 18 27Vac 10 50 60Hz 4 5VA Display 4 digit red LED s digit height 14mm Keys 3 mechanical keys Raise Lower F Accuracy 0 2 f s at 25 C ambient temperature 76 72 36 30 69 5 43 83 52 9 5 1 INSTALLATION Dimensions and cut out Panel mounting Panel mounting Fix the device with the bracket ...

Страница 2: ...IPTION OF FACEPLATE Function key Gives access to different configuration stages Confirms any parameter changes Standard 18 to 27 Vac 11 to 27Vdc 10 50 60 Hz 4 5 VA max not isolated from sensor input Linear Input V Outputs Pt100 PTC NTC 3 1 2 2 1 Linear Input I 4 1 2 10 8 9 7 Out1 Out2 Power supply 11 12 Outputs TC 2 1 4 2 3 1 Ri 50Ω 4 20mA Linear input with 2 wire transmitter PWR PV display Indica...

Страница 3: ...u 5 Standard Configuration Menu Enable selftuning autotuning softstart Proportional band for heating or hysteresis in regulation ON OFF Integral heating time Derived heating time Maximum limit heating power S tu Autotuning Selftuning Softstart continuous 0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 0 999 9 f s 0 00 99 99 min 0 00 99 99 min 0 0 100 0 0 10 0 4 0 1 0 100 0 Default Cust...

Страница 4: ...min Reset power 100 0 100 0 999 scale points Hysteresis for alarm 2 Hysteresis for alarm 1 999 scale points Hysteresis for alarm 3 Integral cooling time 0 00 99 99 min Derived cooling time 0 00 99 99 min Manual reset 999 999 scale points Maximum limit cooling power 0 0 100 0 N B the LBA alarm is excluded for ON OFF controls 13 6 PROGRAMMING and CONFIGURATION F If the Inc Dec F keys are not pressed...

Страница 5: ...YP Signal type Scale Max scale range 24 0 10V linear 1999 9999 25 2 10V linear 1999 9999 SENSOR VOLTAGE 10V or TRANSMITTER CAL 6 InP Input settings Digital filter on main input Digital filter on display of process variable acts as hysteresis Decimal point position for main input scale not available for TC RTD PTC scales Minimum limit of main input scale Maximum limit of main input scale Main input...

Страница 6: ...ycle time OUT3 relay or logic HEAT or COOL 0 200 sec Prot Pro Protection code Pro Display Change 0 SP alarms OutP SP alarms 1 SP alarms OutP SP 2 SP SP 3 SP 4 disable InP Out 8 disable CFG 16 disable SW turn on turn off To activate the turn off SW function press keys F for 5 secs in P V To return to normal functioning press key F for 5 secs 15 OUT 1 Attribution of reference signal HEAT COOL AL1 AL...

Страница 7: ...by means of the TRAFO1 transformers specified in the manual one for each device when The application is unknown Multiple devices have input signals that are not isolated from one another such as for example non isolated grounded thermocouples transducers or transmitters powered by a single supply linear inputs with voltage or current not isolated from one another It is a general rule that devices ...

Страница 8: ... remote switches contactors relays thyristor power units particularly if phase angle type motors etc in the same cabinet avoid dust humidity corrosive gases and heat sources do not close the ventilation holes working temperature must be in the range of 0 50 C If the device has faston terminals they must be protected and isolated if the device has screw terminals wires should be attached at least i...