gefran 40T 72 PID Скачать руководство пользователя страница 6

Fault action

(definition of state

in case of broken

sensor) alarms

AL1, AL2, AL3.

Select intrinsic

safety

1) In case of broken sensor, the logic state of the alarm assumes the logic value selected without consideration of

alarm type (direct or reverse): ON = alarm active, OFF = alarm inactive.

2) Alarms are assigned to available outputs by setting codes r.o.1, r.o.2, r.o.3.

rEL

Alarm

Alarm

Alarm

1

2

3

0

OFF

OFF

OFF

1

ON

OFF

OFF

2

OFF

ON

OFF

3

ON

ON

OFF

4

OFF

OFF

ON

5

ON

OFF

ON

6

OFF

ON

ON

7

ON

ON

ON

Cycle time OUT1 relay or

logic = HEAT or COOL

Cycle time OUT2 relay or

logic = HEAT or COOL

0. ... 200 sec

0. ... 200 sec

10

Cycle time OUT3 relay or

logic = HEAT or COOL

0. ... 200 sec

• Prot 

Pro

Protection code

Pro

Display

Change

0

SP, alarms, OutP

SP, alarms

1

SP, alarms, OutP

SP

2

SP

SP

3

SP

+ 4 disable InP, Out
+ 8 disable CFG
+ 16 disable “SW turn on – turn off”

To activate the turn off SW function, press keys

F + 

for 5 secs. in P.V.
To return to normal functioning, press key F for 5 secs.

15

OUT 1

Attribution of

reference signal: HEAT,

COOL, AL1, AL2, AL3

+16 for logic level denied at output

OUT 2

Attribution of

reference signal: HEAT,

COOL, AL1, AL2, AL3

r.o.x MAIN logic output function, relay (OUT1)

0

HEAT (heating control output)

1

COOL (cooling control output)

2

AL1 - alarm 1

3

AL2 - alarm 2

4

AL3 - alarm 3

5

-

6

LBA - alarm LBA

7

(AL1) OR (AL2)

8

(AL1) OR (AL2) OR (AL3)

9

(AL1) AND (AL2)

10

(AL1) AND (AL2) AND (AL3)

2

0

OUT 3

Attribution of

reference signal: HEAT,

COOL, AL1, AL2, AL3

Содержание 40T 72 PID

Страница 1: ...pply option 18V 10 50mA 1 2V for potentiometer 100 Ω version P77 Power supply not isolated from sensor input 11 27Vdc 18 27Vac 10 50 60Hz 4 5VA Display 4 digit red LED s digit height 14mm Keys 3 mechanical keys Raise Lower F Accuracy 0 2 f s at 25 C ambient temperature 76 72 36 30 69 5 43 83 52 9 5 1 INSTALLATION Dimensions and cut out Panel mounting Panel mounting Fix the device with the bracket ...

Страница 2: ...IPTION OF FACEPLATE Function key Gives access to different configuration stages Confirms any parameter changes Standard 18 to 27 Vac 11 to 27Vdc 10 50 60 Hz 4 5 VA max not isolated from sensor input Linear Input V Outputs Pt100 PTC NTC 3 1 2 2 1 Linear Input I 4 1 2 10 8 9 7 Out1 Out2 Power supply 11 12 Outputs TC 2 1 4 2 3 1 Ri 50Ω 4 20mA Linear input with 2 wire transmitter PWR PV display Indica...

Страница 3: ...u 5 Standard Configuration Menu Enable selftuning autotuning softstart Proportional band for heating or hysteresis in regulation ON OFF Integral heating time Derived heating time Maximum limit heating power S tu Autotuning Selftuning Softstart continuous 0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 0 999 9 f s 0 00 99 99 min 0 00 99 99 min 0 0 100 0 0 10 0 4 0 1 0 100 0 Default Cust...

Страница 4: ...min Reset power 100 0 100 0 999 scale points Hysteresis for alarm 2 Hysteresis for alarm 1 999 scale points Hysteresis for alarm 3 Integral cooling time 0 00 99 99 min Derived cooling time 0 00 99 99 min Manual reset 999 999 scale points Maximum limit cooling power 0 0 100 0 N B the LBA alarm is excluded for ON OFF controls 13 6 PROGRAMMING and CONFIGURATION F If the Inc Dec F keys are not pressed...

Страница 5: ...YP Signal type Scale Max scale range 24 0 10V linear 1999 9999 25 2 10V linear 1999 9999 SENSOR VOLTAGE 10V or TRANSMITTER CAL 6 InP Input settings Digital filter on main input Digital filter on display of process variable acts as hysteresis Decimal point position for main input scale not available for TC RTD PTC scales Minimum limit of main input scale Maximum limit of main input scale Main input...

Страница 6: ...ycle time OUT3 relay or logic HEAT or COOL 0 200 sec Prot Pro Protection code Pro Display Change 0 SP alarms OutP SP alarms 1 SP alarms OutP SP 2 SP SP 3 SP 4 disable InP Out 8 disable CFG 16 disable SW turn on turn off To activate the turn off SW function press keys F for 5 secs in P V To return to normal functioning press key F for 5 secs 15 OUT 1 Attribution of reference signal HEAT COOL AL1 AL...

Страница 7: ...by means of the TRAFO1 transformers specified in the manual one for each device when The application is unknown Multiple devices have input signals that are not isolated from one another such as for example non isolated grounded thermocouples transducers or transmitters powered by a single supply linear inputs with voltage or current not isolated from one another It is a general rule that devices ...

Страница 8: ... remote switches contactors relays thyristor power units particularly if phase angle type motors etc in the same cabinet avoid dust humidity corrosive gases and heat sources do not close the ventilation holes working temperature must be in the range of 0 50 C If the device has faston terminals they must be protected and isolated if the device has screw terminals wires should be attached at least i...

Отзывы: