Instruction Manual
SBI-COP/DN-AGy Card • 1
Eng
lish
Error class
Error code
Additional code (hex)
Meaning
0x06
0x02
0x0000
Parameter doen’t exist
0x08
0x00
0x0000
Generic error
0x06
0x01
0x0000
Read only parameter
0x08
0x00
0x0022
Acces failed because of present device state
0x06
0x09
0x0030
Minimum value
0x06
0x09
0x0031
Maximum value
0x05
0x04
0x0000
SDO time_out
0x05
0x04
0x0001
Invalid command
0x06
0x09
0x0030
Invalid value
3.5 Alarms
Fieldbus alarms
The bus failure is signaled via the “bF Bus fault”. alarm. As for CANopen,
the possible failure causes are:
- “Bus-off” condition of the CAN line;
- the “Life Guarding” threshold has been overcome.
The
I.754 Bus Flt Holdoff
parameter allows to set a delay time for the
intervention of the “bF Bus fault”. alarm.
Drive alarm handling
The optimization or the recovery of the drive alarm conditions are signaled
via the emergency signal.
This service is active only in “Operational” condition. There is no signal
for those events occurred when the communication condition is not “Op-
erational”.
Alarm reset
The alarm reset is one of the drive standard functions. It is possible to reset
the drive via SDO by sending the value 1 to the
H.501 IPA1030
parameter,
or via PDO by mapping the Alarm reset function on a virtual digital input.