background image

 
 

WARNING!! In case of alarm: 

1) 

extinguish all naked flames 

2) 

turn off the gas supply at the gas emergency control and/or,

 

with a LPG supply, the storage tank 

3) 

do not switch on or off any electrical lights. Do not activate

 

any electrically powered devices 

4) 

Open  both  doors  and  windows  to  increase  room  ventilation

 

If  the  alarm  stops,  it  is  necessary  to 

identify the alarm reason

 

and act accordingly. 

If the alarm condition continues and the cause of the leak is not

 

apparent and/or cannot be corrected, 

vacate the premises and

 

immediately notify the gas emergency service. 

 

ТЕХНИЧЕСКИЕ

 

ХАРАКТЕРИСТИКИ

 

Напряжение

 

питания

~ 230 

В

, 50 

Гц

 / =12 

В

, 2,5 

Вт

 

Потребляемый

 

ток

не

 

более

 20 

мА

 

Рабочая

 

температура

-10°C ... +40°C 

Относительная

 

влажность

30% ... 90%  

Срабатывание

 

аварийного

 

сигнала

 

откалибровано

 

на

 

обнаружение

 

наличия

 

газа

 

в

 

концентрации

 

до

 10 % 

ниже

 

НПВ

 (

нижний

 

предел

 

взрываемости

). 

Временная

 

задержка

 

при

 

включении

:

 

около

 1 

минуты

 

Аварийный

 

сигнал

 

и

 

временная

 

задержка

 

срабатывания

 

реле

 (GAMMA 654-O): 

около

 20 

секунд

 

Акустическая

 

сигнализация

85 

дБ

 (A) 

на

 

расстоянии

 1 

метр

 

Электрический

 

сигнал

 

самодиагностики

 

для

 

проверки

 

возможной

 

неисправности

 

Класс

 

защиты

 

корпуса

IP42 

Вход

 

дистанционного

 

устройства

 (GAMMA 654-O) 

 

TECHNICAL CHARACTERISTICS 

Power supply 

230Vac, 50Hz/12Vdc 2,5 W 

Power dissipation 

20mA max 

Operation temperature 

-10°C ... +40°C 

Humidity 

30% ... 90% 

Alarm intervention calibrated to detect gas up to 10% of the

 

L.E.L.(Low Explosion Limit). 

Time delay at switching on 

about 1 minute 

Alarm and relay time delay (GAMMA 654-O) about 20 seconds 

Acoustic signalisation 

85 dB (A) in 1 meter 

Electrical self-diagnosis signal for eventual abnormalities 

Rated to 

IP42 

Input remote unit (GAMMA 654-O) 

Содержание 654-O/G

Страница 1: ...supply Gas detected 654 O M 230 12 Methane 654 O G 230 12 LPG 656C M 230 12 Methane 656C G 230 12 LPG GAMMA 654 O M GAMMA 654 O G GAMMA 656C M 656C G GAMMA 654 O M GAMMA 654 O G GAMMA 656C M GAMMA 65...

Страница 2: ...to be put out of order or re send to Geca S r l for a complete substitution of the device With that aim for this purpose on the cover you will find a label on which have to be indicated the maturity...

Страница 3: ...n the heating phase During this time all the detection functions will be inhibited GAMMA 654 O M GAMMA 656C M 30 GAMMA654 O G GAMMA 656C G 30 1 4 METHANE Detector L P G Detector INSTALLATION Attention...

Страница 4: ...g Directly over the sink or the gas device In little locals where can be utilised alcohol ammonia spray bottles of gas or other substances with flying solvents In low ventilated environments Near to w...

Страница 5: ...M GAMMA 652C G GAMMA 652 O M GAMMA 652 O G 3 5 6 REMOTE CONNECTION The central unit has two clamps 5 6 active in closeness to be connected with an remote sensor GAMMA 656C M or with GAMMA 656C G or w...

Страница 6: ...LVE 4 OPERATIONAL WITH NORMALLY CLOSED VALVE ELECTRICAL CONNECTION WITH MORE THEN ONE CENTRAL UNITS The following plans mentioned shows the connection in between two central units with an single elect...

Страница 7: ...MA 656C G OPERATING CONTROLS After the installation it is possible to check the correct use of the instrument by pushing for at least 2 seconds the TEST button on the GAMMA 654 O M or GAMMA 654 O G bo...

Страница 8: ...rms We recommend to ventilate the room where products like these can be used Note that the detector is not able to detect gas leaking outside the room where it is installed neither inside walls or und...

Страница 9: ...not apparent and or cannot be corrected vacate the premises and immediately notify the gas emergency service 230 50 12 2 5 20 10 C 40 C 30 90 10 1 GAMMA 654 O 20 85 A 1 IP42 GAMMA 654 O TECHNICAL CHA...

Страница 10: ...__________ TO COMPILE BY THE INSTALLER Installation date _____________________________________ Substitution date ____________________________________ Installation local _______________________________...

Страница 11: ...chase date Any damages caused by tampering and incorrect use or installation will be not covered by warranty The warranty is valid only if is full compiled In case of defects covered by warranty the p...

Страница 12: ...srl it 0134108 2 710 1509 GECAs r l GECA S r l reserves the right to make any aesthetic or functional modification to the without prior notice at any time WARRANTY CERTIFICATE TO COMPILE AND SEND IN C...