background image

SYSTEM SENSOR CARBON MONOXIDE DETECTORS 

CO1224T/CO1224TR

Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.

5172

NOT TO BE USED FOR INSTALLATION PURPOSES.

CATALOG NUMBER

Description

The  System  Sensor  CO1224T  and  CO1224TR 

(round) Carbon Monoxide (CO) Detectors use a highly 

accurate and reliable electrochemical sensing cell to 

provide early warning of dangerous CO levels.  
With RealTest

®

 technology, the CO gas sensing cell 

used in the CO1224T and CO1224TR CO detectors 

can be tested using a CO gas agent, fully meeting 

the requirements of NFPA 720: 2009. Simply put the 

detector into RealTest mode, spray a small amount of 

CO into the detector per the installation instructions, 

and within seconds the detector will alarm, indicating 

successful gas entry. (See the reverse page or the user 

manual for complete instructions.)
When dangerous amounts of CO are detected, the 

CO1224T and CO1224TR detectors alert residents by 

sounding and flashing a temp 4 signal alarm. With 24/7 

central station monitoring, residents are guaranteed 

protection whether they are away from home, sleeping, 

or already suffering from the effects of CO.
The CO1224T and CO1224TR are designed for system 

operation.  These detectors are fully listed to UL 2075 

and offer a code-required trouble relay to send a sensor 

failure or end-of-life signal to the control panel and the 

central station. The CO1224T and CO1224TR also use 

SEMS-type terminal Philips head screws for quicker and 

more positive wiring connections and code-required 

wiring supervision. 

Features

RealTest

• 

®

 enables a functional test using canned 

CO

Full compliance with UL 2075

• 

A code-required trouble relay

• 

Wiring supervision with SEMS terminals

• 

A six-year end-of-life timer

• 

12/24 VDC

• 

A low current draw of 20 mA in standby and 40 

• 

mA in alarm
Versatile mounting for wall and ceiling

• 

Accurate  and  reliable  electrochemical  sensing 

• 

technology

Optional CO-PLATE CO Detector Replacement 

• 

Plate to upgrade previously installed competitor 

detectors to the CO1224T

With a low current draw, these detectors enable more 

devices to be connected to the panel, limiting the need 

to purchase extra power supplies or more expensive 

panels. As 12/24 VDC detectors, the CO1224T and 

CO1224TR will operate on most industry security and 

fire alarm control panels.

Architectural/Engineering Specifications

Carbon monoxide detector shall be a System Sensor 

model  number  CO1224T  or  CO1224TR  listed  to 

Underwriters Laboratories UL 2075 for Gas and Vapor 

Detectors and Sensors. The detector shall be equipped 

with a sounder and a trouble relay. The detector’s base 

shall be able to mount to a single-gang electrical box 

or direct (surface) mount to the wall or ceiling. Wiring 

connections shall be made by means of SEMS screws. 

The detector shall provide dual color LED indication 

that blinks to indicate normal standby, alarm, or end-

of-life.  When  the  sensor  supervision  is  in  a  trouble 

condition, the detector shall send a trouble signal to 

the panel. When the detector gives a trouble or end-of-

life signal, the detector shall be replaced. The detector 

shall provide a means to test CO gas entry into the 

CO sensing cell. The detector shall provide this with a 

test mode that accepts CO gas from a test agent and 

alarms immediately upon sensing CO entry.

Отзывы: