Bock LR Leistungsregler
Bock LR Capacity regulation
Bock LR Régulation de puissance

3

Bild 3

 Zylinderpaar-Abschaltung an Vierzylinder-

Verdichtern: 1 Zylinderpaar abschaltbar.

Bild 4

 Zylinderpaar-Abschaltung an Sechs-/Acht-

zylinder-Verdichtern: maximal sind 2 bzw. 3 
Zylinderpaare abschaltbar.

Bild 5

 Empfohlene Anordnung der LR-Leistungs-

regler an Mehrzylinder-Duplex-Aggregaten

Fig. 3

 Cylinder shut-down in pairs for four cylinder 

compressors: 1 pair of cylinders can be shut-down.

Fig. 4

 Cylinder shut-down in pairs for six-/eight 

cylinder compressors: max. 2 or 3 pairs of cylinders 
can be shut-down.

Fig. 5

 Recommended arrangement of LR capacity 

regulator at multi-cylinder duplex unit

Fig. 3

 Mise hors circuit par paire de cylindres sur 

des compresseurs à 4 cylindres. 1 paire de cylindres 
peut être mise hors circuit.

Fig. 4

 Mise hors circuit par paire de cylindres sur des 

compresseurs à 6/8 cylindres. 2 ou 3 paires de cylin-
dres au maximum peuvent être mises hors circuit.

Fig. 5

 Disposition recommandée du régulateur de puis-

sance LR sur les groupes Duplex plusieurs cylindres.

2.3 

Anordnung

2.4  Funktionsprüfung

Aufgrund seines Aufbaus lässt sich die Regel-
funktion des Ventils nur im eingebauten Zustand 
während des Verdichterbetriebs prüfen.

2.4  Control function

On account of its structure, the control function 
of the valve can only be tested when correctly 
installed during compressing operation.

2.3 

Arrangement

2.3 

Disposition

2.4  Remarque :

Par suite de sa construction, la fonction de régu-

lation de la vanne ne peut être vérifiée qu' à l état 

monté pendant le fonctionnement du compresseur.

Verdichter für Zylinderabschaltung

Aufgrund ihrer Anordnung können Zylinder nur 
paarweise abgeschaltet werden.

Verdichtertyp 

max. 

Regelstufen

 

Anzahl 

in % der Voll-

 

der LR 

leistung

HG(HA)34, 4, 5, 6 

50

HG7 

66 / 33

HG8 

75 / 50 / 25

AM4, 5 

50

F4, 5, 14 / FK40 

50

F16 / FK50 

66 / 33

Compressors of cylinder shut-down

The cylinders are shut-down in pairs correspon-
ding to their arragement in pairs.

Type 

max. 

Regulation

 

number 

as % of full

 

of LR 

capacity

HG(HA)34, 4, 5, 6 

50

HG7 

66 / 33

HG8 

75 / 50 / 25

AM4, 5 

50

F4, 5, 14 / FK40 

50

F16 / FK50 

66 / 33

Compressures pour mise hors circuit  

 

des cylindres

Les cylindres seront mis hors circuit par paire en 
fonction de leur disposition en paire.
Type 

Nombre 

Degrés de régla-

 

maxi. 

ge en % de la puis-

 

de LR 

sance maximale

HG(HA)34, 4, 5, 6 

50

HG7 

66 / 33

HG8 

75 / 50 / 25

AM4, 5 

50

F4, 5, 14 / FK40 

50

F16 / FK50 

66 / 33

3.1  Kombination von Zylinderpaarabschal-
 

tung mit Aggregatabschaltung

Beim Einsatz von Duplex-Verdichtern DHG, DHA
und DAM mit Leistungsregulierung lässt sich bei
Abschaltung eines Verdichters während des
Betriebs des laufenden Verdichters mit Leistungs-
regler eine noch feinere Regelung erreichen.

3.1  Combination of compressor shut-down  
 

in pairs with unit shut-down

When using duplex compressors type DHG, DHA 

and DAM with capacity regulation, even finer 

capacity regulation can be achieved by shutting 
down one compressor, while the other compres-
sor operates with a capacity regulator.

3.1  Combinaison de mise hors circuit du
 

compresseur et régulation de puissance

En utilisant les compresseurs duplex DHG, DHA et 

DAM à régulation de puissance, il est possible d' 
obtenir un réglage encore plus fin en metttant un 

compresseur hors circuit lors du service du compres-
seur en marche ayant un régulateur de puissance.

Bild 3, Fig. 3

Bild 4, Fig. 4

Bild 5, Fig. 5

Содержание Bock LR

Страница 1: ...iable service friendly quality product from Bock s accessories range In order to make full use of the advantages of efficient capacity regulation throughout the entire service life of your refrigera ting plant it is important that you observe the fol lowing installation and maintenance instructions If you have any questions about installation and operation of the unit simply contact our technical ...

Страница 2: ...oad rates depend on the ratio between the number of working cylinders to the nummber of shut down cylinders The Bock capacity regulation can also be used for operation with NH3 R 717 2 2 Mode of operation full load solenoid is dead suction inlets are open fig 1 partial load solenoid is actuated suction inlets are closed fig 2 2 Régulation de puissance par arrêt de gaz d aspiration mise hors circui...

Страница 3: ...presseur 3 Verdichter für Zylinderabschaltung Aufgrund ihrer Anordnung können Zylinder nur paarweise abgeschaltet werden Verdichtertyp max Regelstufen Anzahl in der Voll der LR leistung HG HA 34 4 5 6 1 50 HG7 2 66 33 HG8 3 75 50 25 AM4 5 1 50 F4 5 14 FK40 1 50 F16 FK50 2 66 33 3 Compressors of cylinder shut down The cylinders are shut down in pairs correspon ding to their arragement in pairs Type...

Страница 4: ...ed may not fall below a minimum level in either full load or partial load operation 4 m s in horizonal pipe sections 8 m s in vertical pipes For this reason we recommend that vertical pipes be staggered into two separate sections fig 6 As a result of falling suction gas speed velocity in partial load operation the pipe elbow B is blocked by an accumulation of oil This increases the gas velocity in...

Страница 5: ...d wesentlich höhere Geschwindigkeiten zu berücksichtigen z B Saugleitung 15 bis 20 m s 5 Steuerungsmethoden tion In plants with extensive pipe systems it is recommended to install an additional oil seperator This reduces the oil circulation period and can have positive effects above all on cold starts with relatively high oil ejection For application with NH3 R 717 much higher speeds have to be co...

Страница 6: ...FK4 LR 84 08574 1 quest sur demande 08573 08576 HG HA 34 2 LR 10 80765 80762 80763 80764 AM5 F 5 FK5 LR 87 08565 1 08568 08569 08571 F14 1165 1365 LR 87 08802 08800 08801 08804 F16 1750 2050 LR 87 08802 08800 08801 08804 F14 1166 1366 LR 92 08810 auf Anfrage on request sur demande 08815 F16 1751 2051 LR 92 08810 auf Anfrage on request sur demande 08815 FK40 50 N TK LR 87 08705 08703 08704 08707 FK...

Страница 7: ...ight with the compres sor e g pipelines bungs union nuts replaced parts etc When starting up do not start the com pressor in a vacuum Only operate the compressor when the whole system has been filled Surface temperatures of more than 100 C are possible on the pressure side respec tively under 0 C on the suction side depending on the operating conditions 8 1 Retrofitting capacity regulators to com ...

Страница 8: ... 2 turn to the right 8 1 8 Evacuate the compressor and switch on 8 1 9 Check power consumption on the drive motor 8 2 Modifying compressors with version LR EG 787 to LR 84 or LR 87 8 2 1 LR system EG 787 compressors AM F FK 4 5 can be replaced by systems LR 84 respectively LR 87 but only complete with cylinder cover 8 2 2 Assembly as described under 8 1 1 to 8 1 9 Priére d observer avant la mise e...

Отзывы: