Entelli-Switch 250 User Setup - SET Menu
—SET SYSTEM CLOCK (pg.13)
—DAYLIGHT SAVINGS ON/OFF
—CLOCK EXERCISER (CDP)
(pg.10 & 15)
—EXER S2 RUNTIME (CDT)
(pg.10 & 14)
—S1 UNDER VOLTAGE (pg.8)
Fail
Restore
—S1 UNDER FREQUENCY (pg.8)
Fail
Restore
—S1 OVER VOLTAGE (pg.11)
Fail
Restore
—S1 OVER FREQUENCY (pg.8)
Fail
Restore
—S2 UNDER VOLTAGE (pg.8)
Fail
Restore
—S2 UNDER FREQUENCY (pg.8)
Fail
Restore
—S2 OVER VOLTAGE (pg.8)
Fail
Restore
—S2 OVER FREQUENCY (pg.8)
Fail
Restore
—SET % PHASE IMBALANCE (VI)
FAIL 5%, RESTORE 3% (pg.13)
—SET PHASE IMBALANCE (VI)
TIME DELAY 30 seconds (pg.13)
SET
USER SETUP
MORE
BACK
1 VAB = ___ 2 VAB = ___
VBC = ___
VBC = ___
VCA = ___
VCA = ___
MORE CFG SET ESC
S1 OK
01: 50
FRI 31 MAY 2003
MORE
TEST
Change adjustable values
through the SET menu.
Enter six digit access code
(The factory assigned six-digit access code
is located on the back of the controller)
Figure 10
Network Communications
(Option)
11
12
13
R1
Output
5
6
7
R1
Output
14
15
16
R2
Output
8
9
10
R2
Output
Contact Rating: 10A @ 277VAC or 30VDC
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
PROG 1
PROG 2
GRD (Input Sink)
LS OUT
NIA OUT
ELEV. PRE. OUT
ALARM OUT
STE OUT
MOTOR DISC. OUT
TMS IN
INHIB. > S1
INHIB. > S2
LS IN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
+12V (Output Source)
LN OUT
L4 OUT
L3 OUT
L2 OUT
L1 OUT
YN IN
YE IN
TSNL IN
Q2/TSL IN
S12 IN
S5 IN
11
12
13
5
6
7
14
15
16
8
9
10
1
2
3
4
Output Contacts
Output Contacts
{
{
From J2/J4
Output
J4-3
41
4
13
12
11
10
9
1
2
3
5
6
7
8
J2-3
N.O. N.C.
To J2/J4 Input
Customer
Input
Voltage
{
WARNING
1 Controller inputs must be relay isolated.
2 Controller ouputs have limited source capability.
Use only GE Zenith - specified output modules.
Entelli-Switch 250
TM
Lithium Battery Exerciser
Battery
Replacement - K-4100 (BR2032)
Service
Life
-
10
Years
+
+
During normal operation
User Access Code Default
-
121212
Product Information www.geindustrial.com
24-Hour Service (773)
299-6600
J4
*
J2
*
* Input and output availability
subject to factory configuration.
R1
R2
—TIME DELAY S2 START (P1)
(pg.11)
—TIME DELAY S2 STABLE (W)
(pg.13)
—LOAD PRESIGNAL TD (T3/W3)
(pg.12)
—LOAD DISCONNECT TD (UMD)
(pg.13)
—ATS OPEN TIME TO S2 (DW)
DELAY units only (pg.10)
—TIME DELAY S1 STABLE (T) (pg.12)
—ATS OPEN TIME TO S1 (DT)
DELAY units only (pg.10)
—S2 STOP DELAY (U) (pg.12)
—CALIBRATE S1 (pg.10)
—CALIBRATE S2 (pg.10)
Optional Accessories
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
17