Entelli-Switch 250 User Setup - CFG Menu
—TIMER EXERCISER (CDT)
1, 7, 14, 28 Day (pg. 10 & 14)
—CLOCK EXERCISER
LOAD OR NO LOAD (CDP)
1, 7, 14, 28, 365 Day (pg. 10 & 15)
—TEST KEY (6)
Maintained/Momentary (pg. 10)
—TRANSFER COMMIT (S13)
ON/OFF (pg. 12)
—AUTO / MANUAL (S5 or S12)
ON/OFF (pg. 12)
—IN-PHASE MONITOR (R50)
ON/OFF (pg. 12)
—S1 OVER VOLTAGE (R1-1 or R1-3)
ON/OFF (pg. 11)
—S1 UNDER FREQUENCY
ON/OFF (pg. 8)
—S2 OVER VOLTAGE
ON/OFF (pg. 8)
—S2 OVER FREQUENCY
ON/OFF (pg. 8)
—PHASE IMBALANCE (VI)
ON/OFF (pg. 13)
—PHASE ROTATION MATCH (R16)
ON/OFF (pg.11)
—LOAD DISCONNECT TD (UMD)
(pg.13)
—TRANSFER ALARM (CTAP)
ON/OFF (pg.10)
—NETWORK (ZNET)
ON/OFF (pg. 13)
CONFIG
USER SETUP
MORE
BACK
1 VAB = ___ 2 VAB = ___
VBC = ___
VBC = ___
VCA = ___
VCA = ___
MORE CFG SET ESC
S1 OK
01: 50
FRI 31 MAY 2003
MORE
TEST
Turn options ON or OFF via
keypad through the CFG menu
Enter six digit access code
(The factory assigned six-digit access code
is located on the back of the controller)
Network Communications
(Option)
11
12
13
R1
Output
5
6
7
R1
Output
14
15
16
R2
Output
8
9
10
R2
Output
Contact Rating: 10A @ 277VAC or 30VDC
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
PROG 1
PROG 2
GRD (Input Sink)
LS OUT
NIA OUT
ELEV. PRE. OUT
ALARM OUT
STE OUT
MOTOR DISC. OUT
TMS IN
INHIB. > S1
INHIB. > S2
LS IN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
+12V (Output Source)
LN OUT
L4 OUT
L3 OUT
L2 OUT
L1 OUT
YN IN
YE IN
TSNL IN
Q2/TSL IN
S12 IN
S5 IN
11
12
13
5
6
7
14
15
16
8
9
10
R1
1
2
R2
3
4
Output Contacts
Output Contacts
{
{
From J2/J4
Output
J4-3
41
4
13
12
11
10
9
1
2
3
5
6
7
8
J2-3
N.O. N.C.
To J2/J4 Input
Customer
Input
Voltage
{
WARNING
1 Controller inputs must be relay isolated.
2 Controller ouputs have limited source capability.
Use only GE Zenith - specified output modules.
Entelli-Switch 250
TM
Lithium Battery Exerciser
Battery
Replacement - K-4100 (BR2032)
Service Life - 10 Years
+
+
During normal operation
User Access Code Default
-
121212
Product Information www.geindustrial.com
24-Hour Service (773)
299-6600
J4
*
J2
*
* Input and output availability
subject to factory configuration.
Figure 10
Optional Accessories
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
16