DIRECT CONNECTION
Order the following Kit for 230/208-volt direct
connection as required:
*Not approved for use on 7000 BTU models.
Review installation instructions provided with power
cord or direct connect kits for detailed assembly
instructions.
If using a sub-base connection, the RAK4002C Junction
Box is also necessary for a complete installation.
17
Installation Instructions
265 VOLT ELECTRICAL CONNECTION OPTIONS
Connection of this 265 V AC product to a branch circuit MUST
be done by direct connection in accordance with the National
Electrical Code. Plugging this unit into a building-mounted exposed
receptacle is not permitted by code.
These models must be installed using the appropriate GE power
supply kit for the branch circuit amperage and the electrical
resistance heater wattage desired. Use the POWER CONNECTION
CHART on page 18 to determine the correct kit required. One of
the following installation methods must be used:
Vous DEVEZ brancher ce produit alimenté par courrant alternatif
de 265 volts au circuit de dérivation par branchement direct
conformément au Code national d’électricité. Le Code n’autorise
pas le branche men td evotr eappareil à une prise exposée
montée sur le bâtiment.
Vous devez installer ces modèles à l’aide de la bonne trousse
d’alimentation électrique GE pour l’ampérage du circuit de
GpULYDWLRQHWODSXLVVDQFHGXFKDXȺDJHjUpVLVWDQFHpOHFWULTXH
désirée. Utilisez le Tableau de contact électrique, page 18, pour
déterminer la bonne trousse requise. Vous devez utiliser l’une des
méthodes suivantes d’installation.
La conexión de este producto de 265 voltios de CA a un circuito
derivado DEBE realizarse mediante una conexión directa de
acuerdo a las indicaciones del NEC. El código no permite enchufar
esta unidad a una caja externa.
Estos modelos deben instalarse utilizando el kit de GE de
suministro de energía adecuado para el amperaje de circuito
derivado y el vatiaje deseado para el calefactor de resistencia
eléctrica. Utilice la TABLA DE CONEXIONES ELÉCTRICAS en la
página 18 para determinar cuál es el kit necesario. Debe utilizarse
uno de los siguientes métodos de instalación.
A. FOR SUBBASE
INSTALLATION
Electrical subbase kits are available to provide a flexible
enclosure for direct connection.
*Not approved for use on 7000 BTU models.
The instructions provided with the selected subbase kit
must be carefully followed. It is the responsibility of the
installer to ensure the connection of components is done
in accordance with these instructions and all electrical
codes.
Branch Circuit and
Proper GE
Power
Unit Amperage Rating
Subbase Kit
Supply Kit
15
RAK204E15
RAK515P
20
RAK204E20
RAK520P
30
RAK204E30
RAK530P*
B. FOR DIRECT CONNECT
INSTALLATION
If an electrical subbase is not used, direct connection to
branch circuit wiring inside the provided junction box must
be done in accordance with the following steps.
Order the following Kit for 265-volt direct connection
as required:
*Not approved for use on 7000 BTU models.
Review installation instructions provided with power
cord or direct connect kits for detailed assembly
instructions.
Branch Circuit and
Power
Unit Amperage Rating
Supply Kit
15
RAK515D
20
RAK520D
30
RAK530D*
Branch Circuit and
Unit Amperage Rating
Power
Supply Kit
15
RAK315D
20
RAK320D
30
RAK330D*