– 18 –
Receptacles/Sub-Bases
Sub-Bases
RAK204U
RAK204D15P
RAK204D20P
RAK204D30P*
RAK204E15
RAK204E20
RAK204E30
Voltage
N/A
230/208
230/208
230/208
265
265
265
Amps
N/A
15
20
30
15
20
30
Receptacle
N/A
NEMA6-15R
NEMA6-20R
NEMA6-30R
NEMA7-15R
NEMA7-20R
NEMA7-30R
230/208 Volt sub-bases include appropriate power cord kit.
265 Volt units are to be direct connected. Cordset through enclosed chaseway into interior sub-base receptacle meets the NEC requirements.
* Not approved for use on 7000 BTU models.
230/208 Volt Line Cord Connected Units
LCDI Power Connection Kit
RAK3153A
RAK3203A
RAK3303A*
Heater KW
2.40/2.32
3.30/3.20
4.70/4.53
Watts
2400/2320
3300/3200
4700/4530
BTUH
8100/7900
11200/10900
16000/15400
Amps
11.0/11.6
15.1/16.0
21.2/22.4
Min. circuit amps
15
20
30
Recommended
protective
device
15 Amp
time delay
fuse or breaker
20 Amp
time delay
fuse or breaker
30 Amp
time delay
fuse or breaker
265 Volt Permanent Connected Units**(Cord set)
RAK5172
RAK5202
RAK5302*
2.40
3.40
4.80
2400
3400
4800
8100
11600
16300
9.9
13.3
18.6
15
20
30
15 Amp
time delay
fuse
20 Amp
time delay
fuse
30 Amp
time delay
fuse
* Not approved for use on 7000 BTU models.
** To be used with sub-base
230/208 Volt Direct Connection Kit**
RAK4157
RAK4207
RAK4307*
Heater KW
2.40/2.32
3.30/3.20
4.70/4.53
Watts
2400/2320
3300/3200
4700/4530
BTUH
8100/7900
11200/10900
16000/15400
Amps
11.0/11.6
15.1/16.0
21.2/22.4
Min. circuit amps
15
20
30
Recommended
protective
device
15 Amp
time delay
fuse or breaker
20 Amp
time delay
fuse or breaker
30 Amp
time delay
fuse or breaker
265 Volt Direct Connection Kit**
RAK5157
RAK5207
RAK5307*
2.40
3.40
4.80
2400
3400
4800
8100
11600
16300
9.9
13.3
18.6
15
20
30
15 Amp
time delay
fuse
20 Amp
time delay
fuse
30 Amp
time delay
fuse
* Not approved for use on 7000 BTU models.
** To be used with sub-base or connection to building wiring
* Not approved for use on 7000 BTU models.
** To be used with sub-base or connection to building wiring
Power connection kits are required on all Zoneline
®
chassis (see chart below).
The correct kit for the installation is determined by the voltage and amperage of the electrical circuit and the means of connecting the unit to the
building wiring. If the unit is to be plugged into a receptacle, a line cord kit would be used; if the unit is to be permanently connected, a permanent
connection kit would be used. 265 volt cord set units must be installed in compliance with National Electrical Code
®
.
Power connection kits
Required on all models.
See specification sheet
for heater KW and branch
circuit ampacity.
RAK3153A/3203A
230/208 volt line cord
connection kit
RAK4157/4207/4307
230/208 volt universal
power supply kit
RAK5157/5207/5307
265 volt universal power
supply kit
Tandem
230/208V 15 Amp
NEMA6-15R
Perpendicular
230/208V 20 Amp
NEMA6-20R
Large tandem
230/208V 30 Amp
NEMA6-30R
265V 15 Amp
NEMA7-15R
265V 20 Amp
NEMA7-20R;
receptacle used
On 265V sub-base
GE0720-3
265V 30 Amp
NEMA7-30R;
receptacle used
On 265V sub-base
GE073
*