Critical Power
Modifications reserved
Page 25/25
GE_UPS_OPM_VHU_0K7_3K0_XUS_V011.docx
Operating Manual
VH700 UL, VH1000 UL, VH1500 UL, VH2000 UL & VH3000 UL
8
SPECIFICATIONS
VH Series
: 700
1000
1500
2000
3000
Ratings
Voltage Amperes (VA) with computer type load
: 700
1000
1500
1920
3000
Watts (W) with resistive load
: 630
900
1350
1740
2700
Input thermal circuit breaker (A)
: 8
12
18
20
30
Internal input fuse 250V, slow (A)
: 15
15
30
30
30
Input converter
AC input voltage
: 60 - 140 V
Input current waveform
: sinusoidal, EN 61000-3-2 (IEC 555-2) compliant
Input current (A) at nominal input voltage
: 6.6
9.1
13.9
16
24
Input power factor
: 1
Input frequency range
: 45 - 66 Hz
Inrush current
: none
Output converter
AC output voltage
: 100 / 110 / 115 / 120 / 127 V (selectable)
AC output voltage tolerance
: ± 2%
Output frequency
: auto selectable or 50 / 60 Hz, front selectable
Output frequency range
: nominal ± 0.05% unless synchronized to the mains
Output waveform
: sine wave
Harmonic distortion
: < 1% with linear load
Power factor
: 0.9
Crest factor (peak to RMS current)
: suitable for loads with c.f. up to 3:1
Capacity appliance outlets
: max. 20A per outlet (+ 1 high power outlet max. 20A,
on 2000VA model only)
(+ 1 high power outlet max. 30A,
on 3000VA model only)
Bypass
AC input voltage range
: selected output voltage -15% to +10%
Frequency tracking rate
: 2 Hz/sec.
Frequency tracking range
: nominal ± 10% / ± 2% selectable
Phase difference
: < 1º typical (max. 7º during tracking frequency range)
Typical transfer time, msec
: 1
Overload capability
: fully protected against overload and short circuits
Overload behaviour during battery operation
: 110% 4 minutes
: 150% 2 seconds
Overload behavior during bypass operation
: depends on rating of thermal circuit breaker
typical: 125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
Batteries (ratings given for 77ºF)
Nominal voltage (Vdc)
: 36
36
72
72
72
Number / Ah batteries
: 3/7
3/9
6/7
6/9
6/9
Type
: sealed lead acid, maintenance free
Service life
: up to 6 years (depending on use)
Recharge current
: 1.5 A
Battery recharge time
(batt. discharged at 100% load)
: 3 hours for 90% capacity, std battery
Runtime in minutes at typical load (75%)
: 12
12
11
12
7
VA/Watts
250/225
: 22
35
58
70
102
500/450
: 12
18
28
36
48
700/630
: 8
12
21
27
33
1000/900
:
8
13
20
22
1500/1350
:
7
12
12
1920/1740
:
8
8
8
General
Weight UPS (lbs/kg)
: 35/16
37/17
64/29
71/32
77/35
Dimensions UPS (HxWxD) - inch
:
3.4x17.2x18.5
3.4x17.2x21.3
3.4x17.2x23.0
Dimensions UPS (HxWxD) - mm
:
87x438x470
87x438x540
87x438x585
Enclosure / protection
: steel-plastic / IP20
Battery pack
Nominal voltage (Vdc)
: 36
36
72
72
72
Max. Number / Ah battery extension pack
: 3/14
3/14
3/14
3/14
3/14
Weight (lbs/kg)
:
60/27
101/46
Dimensions (HxWxD)
:
3.4x17.2x18.5inch
3.4x17.2x21.3 inch
:
87x438x470 mm
87x438x540 mm
Environment
Safety
: UL 1778, 5
th
Edition
Electromagnetic compatibility
: EN 62040-2
Ambient temperature
: 32 to 104ºF (0 to +40ºC)
Audible noise at 1 meter
: < 45 dB(A), load and temperature dependent
Max. relative humidity
: 95% (non-condensing)