15.2.1
Error During Update
If the EZ Program Store device’s LED is blinking green/amber and the CPU’s Run LED
is blinking, an error was detected before the old data was erased. When the PLC is placed
into Run mode, it continues using the old data.
If the device’s LED is blinking green/amber and the CPU’s Run LED is off, an error
occurred during the transfer after the data in the PLC was erased. Try the update again by
disconnecting and reconnecting the device and pressing the pushbutton. If the second
update fails, contact the update provider for service.
Update errors are reported as USD Flash Read faults in the PLC Fault Table. The first two
bytes of extra fault data describe the fault.
300
GFK-1503E
VersaMax PLC User Manual
For public disclosure
Содержание VersaMax PLC
Страница 1: ...GE Intelligent Platforms GFK 1503E VersaMax PLC User Manual September 2015 For public disclosure ...
Страница 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 317: ......
Страница 318: ...GE Intelligent Platforms 1 800 433 2682 1 434 978 5100 www ge ip com GFK 1503E For public disclosure ...