13.5.3.1
PLC Fault Table Descriptions
PLC Fault
User Action
Backplane communications with PLC fault; lost request
Check that PLC CPU is running normally (usually in Run mode)
†
Check to make sure you are not sending COMMREQs faster than
the Ethernet interface can process them.
†
Bad local application request; discarded request
Check for valid COMMREQ command code.
†
Bad remote application request; discarded request
Try to validate the operation of the remote node.
†
Cannot locate remote node; discarded request
Error reported when message received where IP address cannot
be resolved. Error may indicate that remote host is not operational
on the network. Check that remote host is operational on network
and its addresses are correct.
Comm_req – Bad task ID programmed
Message from PLC for unknown Ethernet interface task. Check
COMMREQ function block.
Comm_req – Wait mode not allowed
Check COMMREQ to make sure sent in no-wait mode.
LAN data memory exhausted – check parms; resuming
The Ethernet interface does not have free memory to process
communications.
†
LAN I/F capacity exceeded; discarded request
Verify that connection limits are not being exceeded.
LAN transceiver fault; Off network until fixed
Ethernet interface is not properly connected to the network. Check
the connection to the network hub or switch.
LAN system-software fault; aborted connection
resuming
Internal system error.
†
LAN system-software fault; restarted LAN IF
LAN system-software fault; resuming
Module software corrupted; requesting reload
Catastrophic internal system error. Contact GE Automation – NA.
Module state doesn’t permit Comm_Req; discarded
COMMREQ received when Ethernet interface cannot process
COMMREQ. Make sure Ethernet interface is configured and online.
Unsupported feature in configuration
Attempt has been made to configure a feature not supported by the
Ethernet interface. Check CPU revision; order upgrade kit for CPU
and/or Ethernet interface.
†
If the problem persists, contact GE Automation – NA.
13.5.4
Checking the Status of the Ethernet Interface
The application program can monitor the status of the Ethernet interface using the status
bits described below. The beginning address of the data is the Status Address entered
when configuring the CPU. Refer to chapter 6, the section,
for details.
Ethernet Communications
GFK-1503E User Manual 265
For public disclosure
Содержание VersaMax PLC
Страница 1: ...GE Intelligent Platforms GFK 1503E VersaMax PLC User Manual September 2015 For public disclosure ...
Страница 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 317: ......
Страница 318: ...GE Intelligent Platforms 1 800 433 2682 1 434 978 5100 www ge ip com GFK 1503E For public disclosure ...