13.6
Troubleshooting Common Ethernet Difficulties
Some common Ethernet errors are described below. Ethernet errors are generally
indicated in the PLC Fault Table and the Ethernet exception log. As previously explained
in Using the PLC Fault Table, PLC Faults generated by the Ethernet interface contain
Ethernet exception events within the extra fault data. See the VersaMax Station Manager
Manual, GFK-1876 for detailed descriptions of Ethernet exception events.
13.6.1
PLC Timeout Errors
When the SRTP traffic to the CPUE05 exceeds the PLC’s ability to process the requests,
PLC Timeout errors may occur. PLC Timeout errors will take down an SRTP Server
connection; in this case, the remote SRTP client must reestablish a new SRTP connection
to the CPUE05.
This error is indicated in the PLC Fault Table as:
Backplane communication with PLC fault; lost request
with exception Event = 8,
Entry 2 = 8
Backplane communication with PLC fault; lost request
(no exception Event)
These errors may also be accompanied by either of the following:
Backplane communication with PLC fault; lost request
with exception
Event = 8,
Entry 2 = 6
LAN system-software fault; resuming
with exception Event = 8,
Entry 2 = 16
The PLC Timeout condition occurs when the CPUE05 cannot process requests within a
specified timeout period. The remedy is to reduce the requests, or increase the processing
capacity in the PLC.
Cause
Corrective Action
Heavy SRTP traffic.
Reduce the size, number, or frequency of SRTP
requests at the remote SRTP client.
Long PLC sweep time.
Modify the PLC application to reduce the PLC
sweep time.
PLC Communication Window set to
LIMITED mode.
Change to RUN-TO-COMPLETION mode.
If none of the above corrective actions is feasible, the timeout interval may be lengthened.
The timeout interval is specified by the “crsp_tmot” Advanced User Parameter. The
default timeout value is 15 seconds. See Configuring Advanced User Parameters in
chapter 6 to change Advanced User Parameter values.
Note that changing this timeout value does not reduce the actual time for the PLC to
process the requests.
Ethernet Communications
GFK-1503E User Manual 269
For public disclosure
Содержание VersaMax PLC
Страница 1: ...GE Intelligent Platforms GFK 1503E VersaMax PLC User Manual September 2015 For public disclosure ...
Страница 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 317: ......
Страница 318: ...GE Intelligent Platforms 1 800 433 2682 1 434 978 5100 www ge ip com GFK 1503E For public disclosure ...