background image

 

 

VersaMax*  

 

IC200BEM003 

GFK-2739  

 

PROFIBUS Master Module

 

April 2012 

 

The VersaMax

*

 IC200BEM003 PROFIBUS Master Module allows a VersaMax 

CPU005, CPUE05 or PROFINET Scanner (PNS) to send and receive data on a 
PROFIBUS-DP V1 network.  

The PROFIBUS Master module provides the following PROFIBUS 
communications features: 

 

Supports all standard data rates  

 

Supports a maximum of 3,584 bytes of input data and 3,584 bytes of output 
data with a VersaMax CPU; a maximum of 1440 bytes of input data and 1440 
bytes of output data with a PNS. 

 

Supports a maximum of 125 PROFIBUS-DP slaves, with a maximum of 244 
bytes of input data and 244 bytes of output data for each slave 

 

Supports Sync and Freeze modes  

 

Supports DP-V1 Read, Write and Alarm messages 

 

Has PROFIBUS-compliant module and network status LEDs 

This module must be located in a VersaMax Communications Carrier. 

The PROFIBUS module receives its firmware upgrades indirectly from the 
head end CPU or PNS using the WinLoader software utility. WinLoader is 
supplied with any updates to the PROFIBUS module software. 

Ordering Information 

IC200BEM003 

VersaMax PROFIBUS Master Module 

IC200CHS006 

VersaMax Communications Carrier 

 

 

Specifications 

PROFIBUS support 

PROFIBUS-DP V1 

Power Consumption 

450mA at +5V 

I/O Data  

 

 

With a CPU

 

A maximum of 3584 bytes of input data and 3584 bytes of output data 

 

With a PNS

 

A maximum of 1440 bytes of input data and 1440 bytes of output data 

 

With either CPU or PNS head end, a maximum of 244 bytes of input data and 244 
bytes of output data for each slave. 

PROFIBUS network addresses 

0 to 125, software-configurable 

Maximum no. of slave devices 

125 

Network data rate 

9.6K up to 12 Mbaud (bit/sec) 

Status information 

Slave Status Bit Array Table 
Firmware Module Revision 
Slave Diagnostic Address 

Module isolation 

Network to Frame ground: 250VAC continuous, 1500VAC for 1 min 
Profibus network to backplane: 1500VAC minimum 

For product standards, general operating specifications, and installation requirements, refer to the 

VersaMax I/O Modules 

Manual

, GFK-1504. 

                                                           

*

 

indicates a trademark of GE Intelligent Platforms, Inc. and/or its affiliates.  All other trademarks are the property 

of their respective owners.

 

Содержание VersaMax IC200BEM003

Страница 1: ... WinLoader is supplied with any updates to the PROFIBUS module software Ordering Information IC200BEM003 VersaMax PROFIBUS Master Module IC200CHS006 VersaMax Communications Carrier Specifications PROFIBUS support PROFIBUS DP V1 Power Consumption 450mA at 5V I O Data With a CPU A maximum of 3584 bytes of input data and 3584 bytes of output data With a PNS A maximum of 1440 bytes of input data and 1...

Страница 2: ...e Master also maintains its own status in the bit corresponding to its network address Slave Diagnostics ID Array If diagnostics are pending the first word of this two word array contains the station address of the first slave that has diagnostics The diagnostics can be read using the Get Device Diagnostics COMMREQ command 4 This clears the word and the master then places the next pending diagnost...

Страница 3: ...D TxD N Receive data transmission data negative 9 Not used 4 Power up the System and Observe the Module LEDs The LEDs indicate the presence of power and show the operating mode and status of the module On initial powerup with no configuration stored the LED display should be as follows For details on the Master module s LED operation refer to the VersaMax PROFIBUS Master User s Manual GFK 2740 LED...

Страница 4: ...aMax PNS version Requires IC200PNS001 PNS002 firmware version 1 10 or later Rx3i PNC version Requires IC695PNC001 firmware version 1 10 or later Rx3i CPU version Requires IC695CPU320 CPU315 CPE305 or CPE310 firmware version 7 13 or later Restrictions and Open Issues Subject Description RX3i PBS301 returns an error response to a VersaMax PBM configured at high baud rate If an RX3i PBS301 is configu...

Страница 5: ... a VersaMax PBM with a VersaMax CPU005 or CPUE05 head end that has been running with a baud rate of 1 5Mbps or greater reconfiguring with a baud of 500Kbps or less will cause PROFIBUS slaves to fail to connect to the PBM To resolve this problem power cycle the CPU To avoid this error when configuring the PBM with a lower baud rate than the current configuration power cycle the VersaMax CPU after c...

Отзывы: