4
PROFIBUS Master Module
GFK-2739
Important Product Information for this Release
Release History
Version
Firmware Release
Date
Comments
IC200BEM003-AA
1.00
March 2012
Initial release
Compatibility
The PROFIBUS Master module requires the following programming software and CPU versions:
Programmer software
Proficy Machine Edition, version 7.0 with SIM7 or later
VersaMax CPU version
Requires IC200CPU005 or IC200CPUE05 firmware version 2.36 or later
VersaMax PNS version
Requires IC200PNS001/PNS002 firmware version 1.10 or later
Rx3i PNC version
Requires IC695PNC001 firmware version 1.10 or later
Rx3i CPU version
Requires IC695CPU320, CPU315, CPE305 or CPE310 firmware version
7.13 or later
Restrictions and Open Issues
Subject
Description
RX3i PBS301 returns an error
response to a VersaMax PBM
configured at high baud rate
If an RX3i PBS301 is configured with DPV1 enabled as PROFIBUS slave
attached to a VersaMax PBM, and the baud rate is configured to 1.5M or
greater, the RX3i PBS cannot respond to the DPV1 alarm acknowledge request
quickly enough when it receives these request messages at a high rate.