background image

4

 

 

PROFIBUS Master Module 

GFK-2739  

 

Important Product Information for this Release 

Release History 

Version 

Firmware Release 

Date 

Comments 

IC200BEM003-AA 

1.00 

March 2012 

Initial release 

Compatibility 

The PROFIBUS Master module requires the following programming software and CPU versions: 

Programmer software 

Proficy Machine Edition, version 7.0 with SIM7 or later 

VersaMax CPU version 

Requires IC200CPU005 or IC200CPUE05 firmware version 2.36 or later 

VersaMax PNS version 

Requires IC200PNS001/PNS002 firmware version 1.10 or later 

Rx3i PNC version 

Requires IC695PNC001 firmware version 1.10 or later 

Rx3i CPU version 

Requires IC695CPU320, CPU315, CPE305 or CPE310 firmware version 
7.13 or later 

 

Restrictions and Open Issues 

Subject 

Description 

RX3i PBS301 returns an error 
response to a VersaMax PBM 
configured at high baud rate 

If an RX3i PBS301 is configured with DPV1 enabled as PROFIBUS slave 
attached to a VersaMax PBM, and the baud rate is configured to 1.5M or 
greater, the RX3i PBS cannot respond to the DPV1 alarm acknowledge request 
quickly enough when it receives these request messages at a high rate. 

 

Содержание VersaMax IC200BEM003

Страница 1: ... WinLoader is supplied with any updates to the PROFIBUS module software Ordering Information IC200BEM003 VersaMax PROFIBUS Master Module IC200CHS006 VersaMax Communications Carrier Specifications PROFIBUS support PROFIBUS DP V1 Power Consumption 450mA at 5V I O Data With a CPU A maximum of 3584 bytes of input data and 3584 bytes of output data With a PNS A maximum of 1440 bytes of input data and 1...

Страница 2: ...e Master also maintains its own status in the bit corresponding to its network address Slave Diagnostics ID Array If diagnostics are pending the first word of this two word array contains the station address of the first slave that has diagnostics The diagnostics can be read using the Get Device Diagnostics COMMREQ command 4 This clears the word and the master then places the next pending diagnost...

Страница 3: ...D TxD N Receive data transmission data negative 9 Not used 4 Power up the System and Observe the Module LEDs The LEDs indicate the presence of power and show the operating mode and status of the module On initial powerup with no configuration stored the LED display should be as follows For details on the Master module s LED operation refer to the VersaMax PROFIBUS Master User s Manual GFK 2740 LED...

Страница 4: ...aMax PNS version Requires IC200PNS001 PNS002 firmware version 1 10 or later Rx3i PNC version Requires IC695PNC001 firmware version 1 10 or later Rx3i CPU version Requires IC695CPU320 CPU315 CPE305 or CPE310 firmware version 7 13 or later Restrictions and Open Issues Subject Description RX3i PBS301 returns an error response to a VersaMax PBM configured at high baud rate If an RX3i PBS301 is configu...

Страница 5: ... a VersaMax PBM with a VersaMax CPU005 or CPUE05 head end that has been running with a baud rate of 1 5Mbps or greater reconfiguring with a baud of 500Kbps or less will cause PROFIBUS slaves to fail to connect to the PBM To resolve this problem power cycle the CPU To avoid this error when configuring the PBM with a lower baud rate than the current configuration power cycle the VersaMax CPU after c...