PROFIBUS Master Module

 

 

3

 

 

GFK-2739

 

 

 

 

Quick Start Guide  

1. 

Install the Communications Carrier on the DIN 
Rail

 by simply clicking it into place.  

Note:

 Connecting carriers must be installed on the 

same section of 35mm x 7.5mm DIN rail.   

The DIN rail must have a conductive (unpainted) 
finish for proper grounding.   

 

 

2. 

Install the Module on the Communications Carrier

.  

 

Turn latch on the 
module to the 
unlocked position.  

 

Align the connector 
and the latch post and 
press the module 
down until the two 
tabs on the bottom of 
the module click into 
place.  

 

Turn the latch to the 
locked position to 
secure the module to 
the carrier. 

3. 

Connect the communications bus to the 

connector on the front of the module. 

The Master module provides a PROFIBUS 
standard female DB9 subminiature connector.  

PROFIBUS Connector Pin Assignments 

Pin 

Signal 

Not used 

Not used 

RxD/TxD-P: Receive data / transmission 
data positive 

CNTR-P: Control signal for repeaters 
(direction control) 

DGND: Data ground 

VP: Supply voltage of the terminating 
resistance (+ 5V) 

Not used 

RxD/TxD-N: Receive data / transmission 
data negative 

Not used 

4. 

Power up the System, and Observe the Module 
LEDs. 

The LEDs indicate the presence of power 

and show the operating mode and status of the 
module. On initial powerup with no configuration 
stored, the LED display should be as follows. For 
details on the Master 

module’s LED operation, 

refer to the 

VersaMax PROFIBUS Master User’s 

Manual, 

GFK-2740. 

LED 

Color 

State 

OK 

Green 

Solid On 

COM 

Off 

NA 

STAT 

Green 

Blinking 3 times fast at 5 Hz, 
8 times at 0.5 

– 1 Hz 

Note:

 

PROFIBUS uses linear bus architecture that requires active bus termination at both ends. Devices in a 
PROFIBUS network connect directly to the bus cable or indirectly via stub lines. For proper network termination, 
the terminating devices must provide and maintain power.  Power is provided by the device on Pin 6 and Ground 
is provided on Pin 5. If power is lost to either terminating device, the network may not operate correctly. Generally, 
the network master device is one of the terminating devices.  The other terminating device may be a critical slave 
device or a separately powered, stand-alone terminator. 

 

Master

 

PROFIBUS Master Module

 

PLC with  

PROFIBUS Slave Module

 

 

Slaves

 

Stub with

 

Slaves

 

Bus 

 

Termination

 

Bus 

 

Termination

 

 

Содержание VersaMax IC200BEM003

Страница 1: ... WinLoader is supplied with any updates to the PROFIBUS module software Ordering Information IC200BEM003 VersaMax PROFIBUS Master Module IC200CHS006 VersaMax Communications Carrier Specifications PROFIBUS support PROFIBUS DP V1 Power Consumption 450mA at 5V I O Data With a CPU A maximum of 3584 bytes of input data and 3584 bytes of output data With a PNS A maximum of 1440 bytes of input data and 1...

Страница 2: ...e Master also maintains its own status in the bit corresponding to its network address Slave Diagnostics ID Array If diagnostics are pending the first word of this two word array contains the station address of the first slave that has diagnostics The diagnostics can be read using the Get Device Diagnostics COMMREQ command 4 This clears the word and the master then places the next pending diagnost...

Страница 3: ...D TxD N Receive data transmission data negative 9 Not used 4 Power up the System and Observe the Module LEDs The LEDs indicate the presence of power and show the operating mode and status of the module On initial powerup with no configuration stored the LED display should be as follows For details on the Master module s LED operation refer to the VersaMax PROFIBUS Master User s Manual GFK 2740 LED...

Страница 4: ...aMax PNS version Requires IC200PNS001 PNS002 firmware version 1 10 or later Rx3i PNC version Requires IC695PNC001 firmware version 1 10 or later Rx3i CPU version Requires IC695CPU320 CPU315 CPE305 or CPE310 firmware version 7 13 or later Restrictions and Open Issues Subject Description RX3i PBS301 returns an error response to a VersaMax PBM configured at high baud rate If an RX3i PBS301 is configu...

Страница 5: ... a VersaMax PBM with a VersaMax CPU005 or CPUE05 head end that has been running with a baud rate of 1 5Mbps or greater reconfiguring with a baud of 500Kbps or less will cause PROFIBUS slaves to fail to connect to the PBM To resolve this problem power cycle the CPU To avoid this error when configuring the PBM with a lower baud rate than the current configuration power cycle the VersaMax CPU after c...

Отзывы: