4-6
VersaMax PROFINET Scanner Manual
– December 2013
GFK-2721A
4
Channel
Error
Type
Diagnosis Alarm
Type
Module
or
Channel
Error
Cause
Fault Text
Recommendation
8
Channel Diagnosis
Appears / Disappears:
Lower limit value
exceeded
Channel
Low Alarm.
Channel value is below
configured Low Alarm
Lower limit
value
exceeded
Bring process value above
configured low alarm level
16
Channel Diagnosis
Appears / Disappears:
Parameterization
Fault
Module
Rejected
Configuration.
The intelligent module
rejected the
configuration due to
one of the parameters
being incorrect.
Module not
Configured
Verify the settings of the module
with the module documentation.
Not all settings allowed by
GSDML in non-GE Intelligent
Platforms IO Controllers are
supported by the module.
17
Channel Diagnosis
Appears / Disappears:
Power supply fault
Module
Loss of field power to
module.
Power supply
fault
Verify
field power
to the
specified module is wired and
energized correctly.
Note: This does
not
apply to the
Power Supply modules on the
PNS.
257
Channel Diagnosis
Appears / Disappears
Channel
Over range fault.
A/D value is saturated
above 99.5 % of
hardware range
Over Range
Correct wiring
-Provide input in correct range
(such as 4-20mA)
-Verify output is within range
(remove shorts)
258
Channel Diagnosis
Appears / Disappears
Channel
Under range fault.
For example, current
mode on an ALG240
with < 2mA input
Under Range
Correct Wiring
-Provide input in correct range
(such as 4-20mA)
-Verify output is within range
(remove shorts)
259
Channel Diagnosis
Appears / Disappears
Module
Nonvolatile Store Fault.
Non-Volatile
Store Failed
There are no corrective actions
for this. Try store again or fix
hardware.
260
Channel Diagnosis
Appears / Disappears
Channel
Wiring Fault.
RTD measurements
are such that wiring
problems are
suspected
Wiring Fault
Verify RTD wiring and
configuration.
261
Channel Diagnosis
Appears / Disappears
Module
Thermistor fault.
The thermistor in the
thermocouple carrier is
out of range
Thermistor
Fault
Verify the thermocouple carrier.
768
Channel Diagnosis
Appears / Disappears:
Loss of PROFIBUS
slave
Channel
A PROFIBUS slave is
not connected to
IC200BEM003
PROFIBUS DP
Master
module
Loss of
PROFIBUS
slave
Check PROFIBUS DB-9
connector and cable on
IC200BEM003 module and the
slave.
or,
Wait for a time when the
PROFIBUS data rate is set very
low.