3-6
VersaMax PROFINET Scanner Manual
– December 2013
GFK-2721A
3
Configuring VersaMax Module Parameters
After adding VersaMax modules to the remote node, their parameters must be configured. For
all VersaMax modules, this includes configuring a set of basic parameters (such as: reference
address, carrier type, report faults). Configuration details for those basic parameters are given
on the following pages.
The VersaMax modules listed below require additional configuration beyond the basic
parameters described in this chapter. Please refer to their module documentation for detailed
parameter information.
Catalog #
Module Description
Document
IC200ALG240
Analog Input Module, 16 Bit Voltage/Current, 1500VAC Isolation, 8 Channels
GFK-1522
IC200ALG620
Analog Input Module, 16 Bit RTD, 4 Channels
GFK-1523
IC200ALG331
Analog Output Module, 16 Bit Voltage/Current, 1500VAC Isolation, 4 Channels
GFK-1559
IC200ALG630
Analog Input Module, 16 Bit Thermocouple, 7 Channels
GFK-1700
IC200BEM003
PROFIBUS DP Master*
GFK-2740
IC200CMM020
Serial Communications Module (Modbus RTU Master)
GFK-2423
IC200MDD841
Mixed Module, 24VDC Positive Logic Input 20 Points / Output 12 Point / (4)
High Speed Counter, PWM, or Pulse Train Configurable Points
GFK-1561
Note that several analog modules, which use jumpers to select voltage/current or output
defaults, require an additional configuration step before editing their parameters. See
“Configuring Analog Modules that have Jumpers” on page 3-8.
Basic Module Parameters
The module parameters define how the IO-Controller
scans and stores the module’s data. For
discrete input or output modules, there is just one address assignment field.
For discrete modules with both inputs and outputs and for analog modules, there are multiple
address assignment fields.
Default values a
re provided by the module’s GSDML file.
Input Data / Output Data:
The address in the IO-
Controller’s reference memory for the
module’s data.
Length:
For discrete modules, the length of the input /output data is fixed and cannot be edited.
For some analog modules, the data length can be edited.