B-28
L60 Line Phase Comparison System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
5D20
...Repeated for Ground Time Overcurrent 3
5D30
...Repeated for Ground Time Overcurrent 4
5D40
...Repeated for Ground Time Overcurrent 5
5D50
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5E00
Ground Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5E01
Ground Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5E02
Ground Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5E03
Ground Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5E04
Ground Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5E05
Ground Instantaneous Overcurrent 1 Block
0 to 65535
---
1
F300
0
5E06
Ground Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5E07
Ground Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5E08
Reserved (8 items)
0 to 1
---
1
F001
0
5E10
...Repeated for Ground Instantaneous Overcurrent 2
5E20
...Repeated for Ground Instantaneous Overcurrent 3
5E30
...Repeated for Ground Instantaneous Overcurrent 4
5E40
...Repeated for Ground Instantaneous Overcurrent 5
5E50
...Repeated for Ground Instantaneous Overcurrent 6
5E60
...Repeated for Ground Instantaneous Overcurrent 7
5E70
...Repeated for Ground Instantaneous Overcurrent 8
5E80
...Repeated for Ground Instantaneous Overcurrent 9
5E90
...Repeated for Ground Instantaneous Overcurrent 10
5EA0
...Repeated for Ground Instantaneous Overcurrent 11
5EB0
...Repeated for Ground Instantaneous Overcurrent 12
Setting Groups (Read/Write Setting)
5F80
Setting Group for Modbus Comms (0 means group 1)
0 to 5
---
1
F001
0
5F81
Setting Groups Block
0 to 65535
---
1
F300
0
5F82
FlexLogic to Activate Groups 2 through 6 (5 items)
0 to 65535
---
1
F300
0
5F89
Setting Group Function
0 to 1
---
1
F102
0 (Disabled)
5F8A
Setting Group Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read Only)
5F8B
Current Setting Group
0 to 5
---
1
F001
0
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
---
---
---
F203
(none)
5F94
Setting Group 2 Name
---
---
---
F203
(none)
5F9C
Setting Group 3 Name
---
---
---
F203
(none)
5FA4
Setting Group 4 Name
---
---
---
F203
(none)
5FAC
Setting Group 5 Name
---
---
---
F203
(none)
5FB4
Setting Group 6 Name
---
---
---
F203
(none)
Wattmetric ground fault settings (read/write grouped, 2 modules)
6050
Wattmetric ground fault 1 function
0 to 1
---
1
F102
0 (Disabled)
6051
Wattmetric ground fault 1 source
0 to 5
---
1
F167
0 (SRC 1)
6052
Wattmetric ground fault 1 voltage
0 to 1
---
1
F234
0 (Calculated VN)
6053
Wattmetric ground fault 1 overvoltage pickup
0.02 to 3.00
pu
0.01
F001
20
6054
Wattmetric ground fault 1 current
0 to 1
---
1
F235
(Calculated IN)
6055
Wattmetric ground fault 1 overcurrent pickup
0.002 to 30.000
pu
0.001
F001
60
6056
Wattmetric ground fault 1 overcurrent pickup delay
0 to 600
s
0.01
F001
20
6057
Wattmetric ground fault 1 power pickup
0.001 to 1.2
pu
0.001
F001
100
6058
Wattmetric ground fault 1 ECA
0 to 360
° Lag
1
F001
0
6059
Wattmetric ground fault 1 power pickup delay
0 to 600
s
0.01
F001
20
605A
Wattmetric ground fault 1 curve
0 to 5
---
1
F236
0 (Definite Time)
605B
Wattmetric ground fault 1 multiplier
0.01 to 2
s
0.01
F001
100
605C
Wattmetric ground fault 1 block
0 to 65535
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 20 of 55)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...