B-78
F35 Multiple Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F131
ENUMERATION: FORCED CONTACT OUTPUT STATE
0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze
F132
ENUMERATION: DEMAND INTERVAL
0 = 5 min, 1 = 10 min, 2 = 15 min, 3 = 20 min, 4 = 30 min,
5 = 60 min
F133
ENUMERATION: PROGRAM STATE
0 = Not Programmed, 1 = Programmed
F134
ENUMERATION: PASS/FAIL
0 = Fail, 1 = OK, 2 = n/a
F137
ENUMERATION: USER-PROGRAMMABLE PUSHBUTTON
FUNCTION
0 = Disabled, 1 = Self-Reset, 2 = Latched
F139
ENUMERATION: DEMAND CALCULATIONS
0 = Thermal Exponential, 1 = Block Interval, 2 = Rolling Demand
F141
ENUMERATION: SELF TEST ERRORS
F143
UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number)
A bit value of 0 = no error, 1 = error
Bitmask
Error
0
Any Self Tests
1
IRIG-B Failure
2
Port 1 Offline
3
Port 2 Offline
4
Port 3 Offline
5
Port 4 Offline
6
Port 5 Offline
7
Port 6 Offline
8
RRTD Communications Failure
9
Voltage Monitor
10
FlexLogic Error Token
11
Equipment Mismatch
12
Process Bus Failure
13
Unit Not Programmed
14
System Exception
15
Latching Output Discrepancy
17
Maintenance Alert 01
18
SNTP Failure
19
Maintenance Alert
20
Maintenance Alert
21
Maintenance Alert
22
Temperature Monitor
23
Process Bus Trouble
24
Brick Trouble
25
Field RTD Trouble
26
Field TDR Trouble
27
Remote Device Offline
28
Direct Device Offline
29
Maintenance Alert
30
Any Minor Error
31
Any Major Error
33
Maintenance Alert
64
Maintenance Alert
65
IEC 61850 Data Set
66
Aggregator Error
67
Unit Not Calibrated
68
Settings Save Error
69
SRAM Data Error
70
Program Memory
71
Watchdog Error
72
Low On Memory
73
Prototype Firmware
74
Module Failure 01
75
Module Failure 02
76
Module Failure 03
77
Module Failure 04
78
Module Failure 05
79
Module Failure 06
80
Module Failure 07
81
Module Failure 08
82
Module Failure 09
83
Incompatible H/W
84
Module Failure 10
85
Module Failure 11
86
Module Failure 12
87
High ENET Traffic
89
Relay Restart
90
FGM Failure
91
FGM Failure
92
FGM Failure
93
FGM Failure
94
FGM Failure
95
FGM Error
96
Maintenance Alert
97
PHY Monitor
98
Storage Media Alarm
99
Wrong Transceiver
100
Power Supply Warning
Bitmask
Error
Содержание UR F35 Series
Страница 10: ...x F35 Multiple Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 F35 Multiple Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 366: ...5 238 F35 Multiple Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 30 F35 Multiple Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 412: ...8 4 F35 Multiple Feeder Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 426: ...10 12 F35 Multiple Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 454: ...A 28 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 608: ...E 10 F35 Multiple Feeder Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 620: ...F 12 F35 Multiple Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 630: ...H 8 F35 Multiple Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 640: ...x F35 Multiple Feeder Protection System GE Multilin INDEX ...