B-52
F35 Multiple Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
A3A0
...Repeated for Digital Counter 5
A3C8
...Repeated for Digital Counter 6
A3F0
...Repeated for Digital Counter 7
A418
...Repeated for Digital Counter 8
PID Regulator (Read/Write Setting) (4 modules)
A500
PID 1 Function
0 to 1
---
1
F102
0 (Disabled)
A501
PID 1 Sample Time
0.05 to 30
sec
0.01
F001
5
A502
PID 1 Process Signal
0 to 65535
---
1
F600
0
A503
PID 1 Setpoint Signal
-99999.99 to 99999.99
---
0.01
F004
0
A505
PID 1 Tracking Signal
0 to 65535
---
1
F600
0
A506
PID 1 Proportional Gain
0.01 to 100
---
0.01
F001
100
A507
PID 1 Setpoint Weighting
0.01 to 1
---
0.01
F001
100
A508
PID 1 Integ Time Const
0 to 600
sec
0.01
F001
100
A509
PID 1 Antiwindup
0 to 1
---
1
F102
0 (Disabled)
A50A
PID 1 AW Time Const
0 to 600
sec
0.01
F001
100
A50B
PID 1 Deriv Time Const
0 to 600
sec
0.01
F001
100
A50C
PID 1 Derivative Limit
1 to 20
---
1
F001
10
A50D
PID 1 Max
-10000 to 10000
---
1
F002
10
A50E
PID 1 Min
-10000 to 10000
---
1
F002
10
A50F
PID 1 T Min
100 to 9999
ms
1
F001
500
A510
PID 1 Dead Time
1 to 20
sec
1
F001
1
A511
PID 1 Block
0 to 4294967295
---
1
F300
0
A513
PID 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A514
PID 1 Events
0 to 1
---
1
F102
0 (Disabled)
A515
...Repeated for PID 2
A52A
...Repeated for PID 3
A53F
...Repeated for PID 4
PID Regulator Actuals (Read Only) (4 modules)
A560
PID 1 Out
0 to 999999
---
1
F004
0
A562
PID 1 Delta Out
0 to 999999
---
1
F004
0
A564
PID 1 Setpoint
-99999.99 to 99999.99
---
0.01
F004
0
A566
...Repeated for PID 2
A56C
...Repeated for PID 3
A572
...Repeated for PID 4
FlexCurves C and D (Read/Write Setting)
A600
FlexCurve C (120 items)
0 to 65535
ms
1
F011
0
A680
FlexCurve D (120 items)
0 to 65535
ms
1
F011
0
Non Volatile Latches (Read/Write Setting) (16 modules)
A700
Non-Volatile Latch 1 Function
0 to 1
---
1
F102
0 (Disabled)
A701
Non-Volatile Latch 1 Type
0 to 1
---
1
F519
0 (Reset
Dominant)
A702
Non-Volatile Latch 1 Set
0 to 4294967295
---
1
F300
0
A704
Non-Volatile Latch 1 Reset
0 to 4294967295
---
1
F300
0
A706
Non-Volatile Latch 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A707
Non-Volatile Latch 1 Events
0 to 1
---
1
F102
0 (Disabled)
A708
Reserved (4 items)
---
---
---
F001
0
A70C
...Repeated for Non-Volatile Latch 2
A718
...Repeated for Non-Volatile Latch 3
A724
...Repeated for Non-Volatile Latch 4
A730
...Repeated for Non-Volatile Latch 5
A73C
...Repeated for Non-Volatile Latch 6
A748
...Repeated for Non-Volatile Latch 7
A754
...Repeated for Non-Volatile Latch 8
A760
...Repeated for Non-Volatile Latch 9
Table B–10: MODBUS MEMORY MAP (Sheet 44 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR F35 Series
Страница 10: ...x F35 Multiple Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 F35 Multiple Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 366: ...5 238 F35 Multiple Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 30 F35 Multiple Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 412: ...8 4 F35 Multiple Feeder Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 426: ...10 12 F35 Multiple Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 454: ...A 28 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 608: ...E 10 F35 Multiple Feeder Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 620: ...F 12 F35 Multiple Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 630: ...H 8 F35 Multiple Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 640: ...x F35 Multiple Feeder Protection System GE Multilin INDEX ...