4.4.8 Set Error Handling?
The
Set Error Handling?
submenu enables the TMO2D to handle inputs it receives that are outside its measurement
range.
Based on directions it receives, the TMO2D can show the errors on the display and force an output high or low.
If you select any choice except
Force to Value?
, the program returns to the
Set Output Response?
entry. The
Force to
Value?
selection enables you to choose a value to which the output will go when a system error occurs. The mA value
must be set between 0 and 25 mA. If you select
Force to Value?
, the program asks for two more entries.
SETUP MENU
Set Error Handling?
Press [YES] to enter the Error Handling submenu.
Enable Error Handling
[YES] no
Use the [NO] or arrow keys to select [YES] to enable Error Handling. Press [YES]
to confirm the selection. (Selecting [NO] returns the display to the Setup Menu.)
System Error Effects
Set Display Response?
Press [YES] to enter the Display Response submenu.
Display System Error?
[YES] no
Use the [NO] or arrow keys to select if the display will show errors. Press [YES] to
confirm the selection.
System Error Effects
Set Display Response?
Press [NO] to proceed to the next submenu.
SYSTEM ERROR EFFECTS
Set Output Response?
Press [YES] to enter the Output Response submenu.
Select Output Effect:
No effect?
Force high?
Force low?
Force to value?
Hold last value?
Use [NO] or the arrow keys to scroll through the choices for output responses. When
you have reached the desired response, press [YES] to confirm the selection.
Output A, Error Value:
mA Value [X.XX]:
Use the numeric keys to enter the desired value. (The number in brackets represents
the previously entered value.) Press [YES] to enter the value, and [YES] again to
confirm the entry.
Output B, Error Value:
mA Value [X.XX]:
Use the numeric keys to enter the desired value. Press [YES] to enter the value, and
[YES] again to confirm the entry.
System Error Effects
Set Output Response?
Press [NO] to proceed to the final submenu.
Содержание TMO2D
Страница 1: ...GE Measurement Control Solutions Gas Moisture TMO2D Digital Display User s Manual ...
Страница 3: ...GE Measurement Control Solutions TMO2D Digital Display User s Manual 910 084 Rev D August 2011 ...
Страница 4: ...ii ...
Страница 10: ...Chapter 1 Features and Capabilities 2 TMO2D Digital Display User s Manual ...
Страница 24: ...Chapter 2 Installation 16 TMO2D Digital Display User s Manual ...
Страница 26: ...Chapter 2 Installation TMO2D Digital Display User s Manual 18 ...
Страница 72: ...Chapter 6 Specifications 64 TMO2D Digital Display User s Manual ...
Страница 74: ...Appendix A Outline and Installation Drawings 66 TMO2D Digital Display User s Manual ...
Страница 86: ...Appendix B Menu Maps 78 TMO2D Digital Display User s Manual ...
Страница 92: ...Appendix B Menu Maps TMO2D Digital Display User s Manual 84 ...
Страница 96: ...Index 88 TMO2D Digital Display User s Manual ...
Страница 98: ...Warranty 90 TMO2D Digital Display User s Manual ...
Страница 100: ......
Страница 101: ......