Telaire Ventostat™ 8000 Series

Ventostat Wiring Diagrams

The Ventostat family of products has two basic configurations. One 
configuration provides three active outputs (CO

2

, RH and temperature) 

and an independent thermistor. It has an output terminal block with pins 
#1, 2 and 3. The other configuration provides only CO

2

 outputs and an 

independent thermistor and has no terminal block with pins 1, 2, and 3 
installed. For electrical wiring and power supply requirements, these two 
configurations are identical; please follow the specific instructions for 
wiring. The recommended wire gauge is 18-22 AWG (1.0 to 0.75 
metric). 

!WARNING!

Ventostat products have three terminal pins that are 

connected inside the sensor to a common/ground: pin 

#2, 5 and 7 on the I/O terminal blocks and pin #2 on the 

power block. Do NOT connect positive (hot)  24 VAC power 

line to terminal number 2 of the terminal block.

Caution!

 

The T8100 Ventostats are either 3-wire or 4-wire type 

configurations, powered by either AC or DC voltage. They 

are not 2-wire or loop-powered devices. Wiring the units as 

2-wire or loop-powered devices will irreparably damage the 

sensors and void the warranty.

Note:

For temperature measurements, Ventostat models contain a 
passive thermistor (terminal pins #4 and 5), which is 
electrically isolated from the other circuitry and should be 
wired independently from active CO2/RH/temperature outputs. 
The thermistor has no connection to the Ventostat common 
ground and/or power.
The active temperature output has the same common (ground) 
as CO

2

 and RH outputs.

Figure 1: Display Unit Wiring for 3-Wire System, AC 

Power

Figure 2: Display Unit Wiring for 4-Wire System, AC 

Power

Figure 3: Non-Display Unit Wiring for 3-Wire System, 

AC Power

Figure 4: Non-Display Unit Wiring for 4-Wire System, 

AC Power

Figure 5: Wiring CO

2

 Sensor Voltage Output to 

Honeywell M7415 Damper Actuator with W7459 Logic 

Module

Содержание Telaire Ventostat 8000 Series

Страница 1: ...on Display Units Jumper Settings for Non Display a and Display b Units Note Example b shows outputs of CO2 4 20 mA and CO2 0 10 V humidity 4 20 mA and active temperature 0 5 V GE Measurement Control 6860 Cortona Dr Suite B Goleta CA 93117 www ge mcs com Basic Installation for Display Units 1 Separate the case into its front and rear sections 2 Secure the rear section of the case to the wall or jun...

Страница 2: ...r line to terminal number 2 of the terminal block Caution The T8100 Ventostats are either 3 wire or 4 wire type configurations powered by either AC or DC voltage They are not 2 wire or loop powered devices Wiring the units as 2 wire or loop powered devices will irreparably damage the sensors and void the warranty Note For temperature measurements Ventostat models contain a passive thermistor termi...

Страница 3: ...ithout stretching or pulling If the length is long enough to create a loop or bind in the tubing it should be shortened 8 To shorten the tubing remove the connectors that attach to the sensor and cut the tubing to length 9 Replace the tubing connectors by using a twisting or screwing motion Verify the connection is secure Note If the tubing length has been shortened be sure the in line filter is r...

Страница 4: ...pied for 4 hours or more for this self calibration system to operate properly Under these conditions ABC Logic should maintain sensor calibration over the lifetime of the sensor The ABC Logic should be turned OFF where a building is continuously occupied 24 hours per day or where there could be significant sources of non occupant related CO2 such as greenhouses breweries and other industrial and f...

Отзывы: