Telaire Ventostat™ 8000 Series

Power Consumption 

Typical 0.7 W at nominal voltage of 24V AC RMS

Temperature Dependence

0.2% FS per °C (±0.11% per °F)

Stability

T8100/T8300 - Single Channel
<2% of FS over life of sensor (15 years)

T8200 - Dual Channel
<5% of FS or <10% reading annual over life of sensor 
(10 years)

Pressure Dependence

0.135% of reading per mm Hg

Certifications

CE and RoHS compliant

Signal Update 

Every 5 seconds

CO

Warm-up Time

< 2 minutes (operational)
10 minutes (maximum accuracy)

Operating Conditions

32°F to 122°F (0°C to 50°C)
0 to 95% RH, non-condensing

Storage Conditions

-40°F to 158°F (-40°C to 70°C)

Flammability Classification

UL94 5VA

Thermistor Type

NTC 10 K

:

thermistor

Thermistor Accuracy

±1°C (15° to 35°C)

RH Sensing Element

Capacitive polymer sensor

RH Range

0% to 99% RH (non-condensing)

RH Accuracy (25°C)

±2.5% RH (20 to 80% RH)
±3.5% RH (<20% and >80% RH)

Active Temperature Accuracy

±0.8°C @ 22°C

Active Temperature Range

0 to 50°C

ABC Logic™ Self Calibration System

ABC Logic™ (Automatic Background Calibration) self calibration 
allows the sensor to continually recalibrate itself when the indoor 
concentrations drop to outside levels while the building is unoccupied. 
Generally a building must be regularly unoccupied for 4 hours or more 
for this self-calibration system to operate properly. Under these 
conditions, ABC Logic™ should maintain sensor calibration over the 
lifetime of the sensor. The ABC Logic™ should be turned OFF where a 
building is continuously occupied 24 hours per day, or where there could 
be significant sources of non-occupant related CO

2

 such as greenhouses, 

breweries and other industrial and food processing applications.

Output

Analog

0 to 5 V, (100 

:

 output impedance)

0 to 10 V (100 

:

 output impedance) and

4 to 20mA (R

L

 maximum 500 

:

) available simultaneously for CO

2

 

output
Digital to analog error ±1%

Warranty/Other

Warranty

18 months parts and labor

This product is covered by one or more of the following patents: 
5,650,624 / 5,721,430 / 5,444,249 / 5,747,808 / 5,834,777 / 5,163,332 /
5,340,986 / 5,502,308 / 6,344,798 / 6,023,069 / 5,370,114 / 5,601,079 /
5,691,704 / 5,767,776 / 5,966,077 / 6,107,925 / 5,798,700 / 5,945,924 /
5,592,147 / 6,255,653 / 6,250,133 / 6,285,290

Warranty Repairs

GE Sensing will repair Telaire product that fails to meet the terms 
provided for in the Return and Warranty Policy Statement (See, http://
www.ge-mcs.com/en/services-and-support.html).Warranty period shall 
start from date of manufacture and be based on product category and 
type of equipment as specified in Table 1: Product Warranty Periods. For 
all warranty repairs, GE Sensing will bear all product repair parts, labor, 
and standard ground shipping charges.

Содержание Telaire Ventostat 8000 Series

Страница 1: ...on Display Units Jumper Settings for Non Display a and Display b Units Note Example b shows outputs of CO2 4 20 mA and CO2 0 10 V humidity 4 20 mA and active temperature 0 5 V GE Measurement Control 6860 Cortona Dr Suite B Goleta CA 93117 www ge mcs com Basic Installation for Display Units 1 Separate the case into its front and rear sections 2 Secure the rear section of the case to the wall or jun...

Страница 2: ...r line to terminal number 2 of the terminal block Caution The T8100 Ventostats are either 3 wire or 4 wire type configurations powered by either AC or DC voltage They are not 2 wire or loop powered devices Wiring the units as 2 wire or loop powered devices will irreparably damage the sensors and void the warranty Note For temperature measurements Ventostat models contain a passive thermistor termi...

Страница 3: ...ithout stretching or pulling If the length is long enough to create a loop or bind in the tubing it should be shortened 8 To shorten the tubing remove the connectors that attach to the sensor and cut the tubing to length 9 Replace the tubing connectors by using a twisting or screwing motion Verify the connection is secure Note If the tubing length has been shortened be sure the in line filter is r...

Страница 4: ...pied for 4 hours or more for this self calibration system to operate properly Under these conditions ABC Logic should maintain sensor calibration over the lifetime of the sensor The ABC Logic should be turned OFF where a building is continuously occupied 24 hours per day or where there could be significant sources of non occupant related CO2 such as greenhouses breweries and other industrial and f...

Отзывы: