Telaire Ventostat™ 8000 Series

Page 3

Sensing Duct CO

Concentrations

Duct-Mounting the Enclosures

Ventostat products can be installed inside the return air ductwork, if 
needed. As an alternative, please consider the T8031 unit. When 
mounting these products inside the ductwork, seal the hole around the 
wires and leave the duct insulation in place to prevent condensation 
which may damage the sensor.

Pitot Tube Installation for T8300 and T8300-D 

Install the mounting bracket, then install the pitot tube assembly as 
follows:

Note:

The length of the Tygon® tubing is 6 ft. (1.8 m) with the 
optional T62892 pitot kit for the T8300. In order to maintain 
optimum accuracy, the tubing should not be lengthened. If the 
sensor is mounted closer than 3 ft. (0.9 m) the excess tubing 
should be shortened to avoid interference with mechanical or 
moving devices.

1.

To mount the pitot tube, drill one 7/8” hole through the duct.

2.

Insert the pitot tube and mark the two remaining holes for the 
mounting screws.

3.

Punch or drill the two marked holes.

4.

Note the direction of airflow in the duct.

5.

Note the marking on the pitot tube flange and insert so that it is 
properly aligned with the airflow.

6.

To ensure an air tight seal, make sure the mounting surface of the 
duct is clear of dirt or obstructions. Then, attach the pitot tube to the 
duct with sheet metal screws or rivets.

7.

Check the length of the tubing before attaching to the sensor. The 
tubing should connect without stretching or pulling. If the length is 
long enough to create a loop or bind in the tubing, it should be 
shortened.

8.

To shorten the tubing, remove the connectors that attach to the 
sensor and cut the tubing to length.

9.

Replace the tubing connectors by using a twisting or screwing 
motion. Verify the connection is secure.

Note:

If the tubing length has been shortened, be sure the in-line filter 
is replaced on the pitot tube connector marked with an “H”.

Accessory Enclosures

Model T1508 Duct Mount Enclosure (Aspiration Box)

The T8100/T8200/T8300 units can be installed inside a Model 1508 
Duct Mount Enclosure.

Model T1552 Outside Air Measurement Enclosure

This NEMA-3R weatherproof enclosure includes thermostat and allows 
installing the sensor in environments with temperatures down to
 -40°F. 

Model T1505 Harsh Environment Enclosure

For extreme environments where the sensor might be subjected to 
condensation or water spray such as those found in greenhouses or 
breweries- NEMA-3R rated.

Ventostat Specifications

Sensing Method

Non-dispersive infrared (NDIR) absorption
Gold-plated optics
Patented ABC Logic self calibration algorithm

CO

2

 Measurement Range

T8100/T8200/T8300
0 to 2000 ppm (0 ppm = 0 V, 4 mA; 2000 ppm = 10/5V, 20 mA)

T8100/T8200/T8300 - 5P models 
0 to 5000 ppm (0 ppm = 0 V, 4 mA; 5000 ppm = 10/5V, 20 mA) 

CO

Accuracy

T8100/T8300 - Single Channel
400-1250 ppm ±30 ppm or 3% of reading, whichever is greater*,**
1250-5000 ppm ±5% of r 30ppm *, **

T8200 - Dual Channel
75 ppm or 10% of reading (whichever is greater)

*Tolerance based on span gas of ±2%
** ABC Logic not deactivated

Power Supply Requirements       

18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected

Содержание Telaire Ventostat 8000 Series

Страница 1: ...on Display Units Jumper Settings for Non Display a and Display b Units Note Example b shows outputs of CO2 4 20 mA and CO2 0 10 V humidity 4 20 mA and active temperature 0 5 V GE Measurement Control 6860 Cortona Dr Suite B Goleta CA 93117 www ge mcs com Basic Installation for Display Units 1 Separate the case into its front and rear sections 2 Secure the rear section of the case to the wall or jun...

Страница 2: ...r line to terminal number 2 of the terminal block Caution The T8100 Ventostats are either 3 wire or 4 wire type configurations powered by either AC or DC voltage They are not 2 wire or loop powered devices Wiring the units as 2 wire or loop powered devices will irreparably damage the sensors and void the warranty Note For temperature measurements Ventostat models contain a passive thermistor termi...

Страница 3: ...ithout stretching or pulling If the length is long enough to create a loop or bind in the tubing it should be shortened 8 To shorten the tubing remove the connectors that attach to the sensor and cut the tubing to length 9 Replace the tubing connectors by using a twisting or screwing motion Verify the connection is secure Note If the tubing length has been shortened be sure the in line filter is r...

Страница 4: ...pied for 4 hours or more for this self calibration system to operate properly Under these conditions ABC Logic should maintain sensor calibration over the lifetime of the sensor The ABC Logic should be turned OFF where a building is continuously occupied 24 hours per day or where there could be significant sources of non occupant related CO2 such as greenhouses breweries and other industrial and f...

Отзывы: