5-296
T60 Transformer Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
c) BREAKER FLASHOVER
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
BREAKER FLASHOVER 1(2)
The detection of the breaker flashover is based on the following condition:
1.
Breaker open,
2.
Voltage difference drop, and
3.
Measured flashover current through the breaker.
Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available across
the breaker.
BREAKER
FLASHOVER 1
BKR 1 FLSHOVR
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BKR 1 FLSHOVR SIDE 1
SRC: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
BKR 1 FLSHOVR SIDE 2
SRC: None
Range: None, SRC 1, SRC 2, SRC 3, SRC 4, SRC 5,
SRC 6
MESSAGE
BKR 1 STATUS CLSD A:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 STATUS CLSD B:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 STATUS CLSD C:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 FLSHOVR V PKP:
0.850 pu
Range: 0.000 to 1.500 pu in steps of 0.001
MESSAGE
BKR 1 FLSHOVR DIFF V
PKP: 1000 V
Range: 0 to 100000 V in steps of 1
MESSAGE
BKR 1 FLSHOVR AMP
PKP: 0.600 pu
Range: 0.000 to 1.500 pu in steps of 0.001
MESSAGE
BKR 1 FLSHOVR PKP
DELAY: 0.100 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BKR 1 FLSHOVR SPV A:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 FLSHOVR SPV B:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 FLSHOVR SPV C:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 FLSHOVR BLOCK:
Off
Range: FlexLogic operand
MESSAGE
BKR 1 FLSHOVR
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
BKR 1 FLSHOVR
EVENTS: Disabled
Range: Disabled, Enabled
Содержание T60
Страница 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 118: ...3 48 T60 Transformer Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 146: ...4 28 T60 Transformer Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 2 T60 Transformer Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 785: ...GE Multilin T60 Transformer Protection System H 9 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...