Table 7: Operational Specifications
Accuracy
+/- 1.0% (typical or less) Full Span
Hysteresis and Deadband
+/- 0.3% Full Span
Repeatability
+/- 0.3% Full Span
Conformity
+/- 0.5% Full Span
Start-Up Drift
Less than 0.02% in first hour
Long Term Drift
Less than 0.003% per month
Position Travel Limits
Rotary: 18 - 140°
Reciprocating: 0.25” - 2.5“ (6 mm - 64 mm)
Note:
Above 2.5” (64 mm) consult factory for
mounting instructions.
Flow Characteristics
Applied in addition to the control valve’s
inherent characteristic.
Linear
Equal Percentage (of 50:1 or 30:1)
Camflex
Quick Opening (inverse of 50:1 equal percent-
age)
User Configurable
Tight Shut Off
0 -20% of input