Series 195 & 295 Smart Positioners

Specifications - Installation and Operating Instructions

Bulletin V  -195/295

SPECIFICATIONS
Input Signal:

4 to 20 mA DC.

Input Impedance: 

460 Ω max @ 20 mA DC.

Enclosure: 

Aluminum.

Air Supply:

35 to 116 psi (2.4 to 8 bar).

Air Connection: 

1/4˝ NPT.

Gage Connection: 

1/8˝ NPT.

Conduit Connection: 

1/2˝ NPT.

Linearity:

±0.5% FS.

Hysteresis:

±0.5% FS.

Sensitivity: 

±0.2% FS.

Repeatability: 

±0.3% FS.

Air Consumption: 

.0004 scfm (.01 LPM) at 20 psig (1.4 bar) supply.

Flow Capacity: 

.32 scfm (9 LPM) at 20 psi (1.4 bar) supply.

Stroke: 

195: 0.19 to 1.38˝ (5 to 35 mm);
295: 0 to 90°. 

Enclosure Rating:

NEMA 4X (IP66).

Temperature: 

Operating: -22 to 185°F (-30 to 85°C).

Weight:

1.8 lb (.82 kg).

Lever: 

195: 39 to 1.57˝ (10 to 40 mm);
295: NAMUR.

The  Series  195  and  295  Smart  Positioners

are  a  compact  way  to  control  the

valve stroke accurately using an input signal of 4 to 20 mA from the controller. In
addition,  a  highly  efficient  microprocessing  operator  built  into  the  product.
Performs various functions such as auto calibration, PID control, alarm and Hart

®

protocol. 

Features

• LCD allows user to directly check the positioner condition in the field.
• Endures severe vibration.
• Operates normally regardless of changes in supply pressure during operation.
• Simple-to-use auto calibration.
• Low air consumption reduces operating cost.
• Compact size allows for installation on small actuators.
• Can be used in low voltage (8.5 V), leaving no limitation in controller.
• Variable orifice is applied in case of a small actuator, the hunting is controlled

to the optimum condition during operation.

• HART

®

communication available for configurating parameters or monitoring the 

valve position.

• Analog feedback signal (4 to 20 mA).
• The adjustment of valve characteristics (linear, quick open, equal percentage)

available.

• Specific flow control is available with setting 16 points at users’ command.
• Tight shut-close and shut-open can be set in the programming menu.
• PID parameters can easily be adjusted in the field without additional

communicator.

• Split ranges such as 4 to 12 mA, with 12 to 20 mA available. 
• The positioner can manually actuate the valve or damper.

195

Series 195

295

HART

® 

is a registered trademark of Hart Communication Foundation.

Series 295

1 57/64˝

[48.00]

1 11/32˝

[34.00]

 5/16˝ [8.00]

2 1/4˝

[57.00]

 15/16˝
[24.00]

3 3/32˝
[78.50]

[101.60]

5 45/64˝ [144.80]

 2 1/2˝
[63.60]

 5 7/16˝ [138.30]

1 27/64˝

[36.00]

 25/64˝
[10.00]

1 3/16˝
[30.00]

25/64˝

[10.00]

5/32˝

[4.00]

CONDUIT ENTRY

1/2 NPT

4X M6 TAP

LCD SCREEN

SMART POSITIONER

CONDUIT ENTRY

1/2 NPT

1 57/64˝

[48.00]

1 11/32˝

[34.00]

 5/16˝ [8.00]

2 1/4˝

[57.00]

 15/16˝
[24.00]

3 3/32˝
[78.50]

 5 1/64˝
[127.32]

5 45/64˝ [144.80]

 2 1/2˝
[63.60]

 5 7/16˝ [138.30]

1 27/64˝

[36.00]

 25/64˝
[10.00]

1 3/16˝
[30.00]

25/64˝

[10.00]

5/32˝

[4.00]

2 37/64˝
 [65.40]

4X M6 TAP

LCD SCREEN

1 59/64˝
 [48.82]

SMART POSITIONER

PROXIMITY CONTROLS

Phone: 219/879-8000

www.dwyer-inst.com

A DIVISION OF DWYER INSTRUMENTS, INC. 

Fax: 219/872-9057

e-mail: [email protected]

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Содержание Proximity 195 Series

Страница 1: ...in low voltage 8 5 V leaving no limitation in controller Variable orifice is applied in case of a small actuator the hunting is controlled to the optimum condition during operation HART communication...

Страница 2: ...bracket meets the above conditions Series 195 can be installed very easily 2 Assemble Series 195 and bracket with bolts Use standard bolts in bolt holes on the backside of the unit 3 After assembling...

Страница 3: ...based on 79 20 mm of actuator stem height If the actuator stem height is higher such as 1 18 30 mm or 1 97 use the table below to check hole positions Ex If H is 30 mm A L should be locked in H 30 ho...

Страница 4: ...id particles Result of being passed through 5 micron or finer filter 3 Does not contain oil or lubricating oil 4 Comply with ANSI ISA 57 3 1975 R1982 or ISA S7 3 1975 R1981 5 Not used beyond the range...

Страница 5: ...ode After connecting the power to the positioner the following is displayed on the LDC in 6 seconds RUN on the bottom line means that the Smart Positioner adjusts valve stroke based on an outside sign...

Страница 6: ...in Two lines appear on the LCD The upper line indicates valve stroke by percentage and the lower line indicates absolute value of inner resistance of the positioner MA means that Manual mode is in ope...

Страница 7: ...rs on LCD 5 Push ESC to return to PV ZERO mode Push ESC twice to return to RUN mode 6 In order to change valve end point push DOWN at PV_ZERO mode and PV_END mode begins 7 Push ENTER at PV_END mode an...

Страница 8: ...this mode users can adjust the first point of characteristic in 16 points The number on the LCD is the valve stroke percentage set to P0 4 Adjust the valve stroke percentage using UP or DOWN 5 Save it...

Страница 9: ...solute resistance value Information Checked on VIEW Mode Error Code MT ERR L MT ERR H CHK AIR RNG ERR C D Code Description and Cause Positioner is improperly installed Positioner lever is not parallel...

Страница 10: ...nc Printed in U S A 7 14 FR RV 443953 00 Rev 4 Usedtime UserSet ENT Enterbutton ManualMode Auto2 Autocal RUNMode ENT 5sec ESC ESC Auto1 ENT BIAS Auto3 ESC ESC V_O ESC ESC Hartver Character KP Endpoint...