Structure

The structure of the 195 is shown below. The Series 295 structure is the same as
the linear model without the feedback lever.

Installation

Tools For Installation

• Hexagonal wrenches
• (+) Screw driver
• (-) Screw driver
• Spanners for hexagon head bolts

Series 195 Installation

Series  195  is  used  for  linear  motion  valves,  such  as  Dwyer  Instruments  globe
valves, using a spring return type diaphragm actuator or piston actuator. The Series
195  consists  of  the  following  components.  Be  sure  that  all  the  components  are
included. 

• Series 195 main body
• Feedback lever and lever spring
• Flange nut (attached on the bottom of main shaft of Series 195 body)
• Four hexagon head bolts M8x1.25P

• Four M8 plate washers

Installing Series 195 with Bracket

It is necessary to make a proper bracket to attach on the actuator yoke.
The most important considerations in the design of the bracket are as follows:
• Series 195 feedback lever should be at 50% of valve stroke.
• Feedback level connection bar of actuator clamp should be connected in the 

position so that the valve stroke and the numbers carved on feedback lever are 
fitted. 

If the bracket meets the above conditions, Series 195 can be installed very easily. 

2. Assemble Series 195 and bracket with bolts. Use standard bolts in bolt holes on
the backside of the unit.

3. After assembling Series 195 and bracket with bolts, attach it using the bolt holes
of the actuator yoke. Do not tighten completely. There must be some space. 

4. Install the bar connected with Series 195’s feedback lever on the actuator clamp.
The  slot  length  between  Series  195’s  feedback  lever  is  .26˝  (6.5mm),  so  the
diameter of the connection bar should be less than .25˝ (6.3 mm). 

5. Connect the air filter regulator with the actuator temporarily. Set supply pressure
of air filter so that the actuator clamp is positioned at 50% of valve stroke. 

6. Insert the connection bar attached on the actuator clamp into the slot of Series
195’s feedback lever. In order to reduce hysteresis, it should appear as shown:

0

100

50

0

100

50

Series 195 Installation Example

0

100

50

When  the  positioner  is  replaced  or  installed  with  the  actuator,
make sure of the following:

• All inputs and supply pressure to the valve, actuator and other instruments must  

be shut down.

• The control valve must be separated from the system with a bypass valve or other 

equipment so that the entire system does not shut down.

• No pressure remains in the actuator.

NOTICE

Page 2

Содержание Proximity 195 Series

Страница 1: ...in low voltage 8 5 V leaving no limitation in controller Variable orifice is applied in case of a small actuator the hunting is controlled to the optimum condition during operation HART communication...

Страница 2: ...bracket meets the above conditions Series 195 can be installed very easily 2 Assemble Series 195 and bracket with bolts Use standard bolts in bolt holes on the backside of the unit 3 After assembling...

Страница 3: ...based on 79 20 mm of actuator stem height If the actuator stem height is higher such as 1 18 30 mm or 1 97 use the table below to check hole positions Ex If H is 30 mm A L should be locked in H 30 ho...

Страница 4: ...id particles Result of being passed through 5 micron or finer filter 3 Does not contain oil or lubricating oil 4 Comply with ANSI ISA 57 3 1975 R1982 or ISA S7 3 1975 R1981 5 Not used beyond the range...

Страница 5: ...ode After connecting the power to the positioner the following is displayed on the LDC in 6 seconds RUN on the bottom line means that the Smart Positioner adjusts valve stroke based on an outside sign...

Страница 6: ...in Two lines appear on the LCD The upper line indicates valve stroke by percentage and the lower line indicates absolute value of inner resistance of the positioner MA means that Manual mode is in ope...

Страница 7: ...rs on LCD 5 Push ESC to return to PV ZERO mode Push ESC twice to return to RUN mode 6 In order to change valve end point push DOWN at PV_ZERO mode and PV_END mode begins 7 Push ENTER at PV_END mode an...

Страница 8: ...this mode users can adjust the first point of characteristic in 16 points The number on the LCD is the valve stroke percentage set to P0 4 Adjust the valve stroke percentage using UP or DOWN 5 Save it...

Страница 9: ...solute resistance value Information Checked on VIEW Mode Error Code MT ERR L MT ERR H CHK AIR RNG ERR C D Code Description and Cause Positioner is improperly installed Positioner lever is not parallel...

Страница 10: ...nc Printed in U S A 7 14 FR RV 443953 00 Rev 4 Usedtime UserSet ENT Enterbutton ManualMode Auto2 Autocal RUNMode ENT 5sec ESC ESC Auto1 ENT BIAS Auto3 ESC ESC V_O ESC ESC Hartver Character KP Endpoint...

Отзывы: