Masoneilan SVi1000 Positioner Quick Start Guide
=
|
25
© 2016 General Electric Company. All rights reserved
.
Tools required:
M5 Hex Key
M4 Hex Key
M3 Hex Key
To mount the SVi1000:
1. Attach the mounting bracket to actuator (Figure 9).
Long Side
Mounting
Holes
Mounting
Bracket
Mount the long end of the mounting
bracket to the left when facing the
actuator, if possible.
Valve Position Take
Off Shaft
Flat Head Socket Cap Screw, 5/
16"-18UNC X 0.62" Long
Figure 9
Rotary Mounting Bracket to Valve Actuator
2. Bolt the extension shaft to the valve position take-off shaft (Figure 10).
Tighten the
M4 screw
(one shown)
Install with a
flat head socket
cap screw,
1/4"-28 UNF
Magnet
Holder
Assembly
Extension
Shaft
Valve Position
Take Off
Shaft
Figure 10
Extension Shaft to the Valve Position Take-off Shaft