GEK-105593C
50
6.6. COMMUNICATIONS
The test is to check that the 3 connectors in the relay allow communication with the relay. To do this it is
necessary to use a computer and a connector suitable to establish the connections between PC and relay
which are shown in figure 8.
The communication parameters which have to be set for the computer are the relay's default settings, as
follows:
Relay number:
1
Remote port baud rate: 19200
Local port baud rate:
19200
Remote stop bits:
1
Local stop bits:
1
This test is carried out at the minimum and maximum voltage that the relay will allow (
±
20% of the nominal
voltages).
6.7. RELAY SETTING
When it leaves the factory the relay has some default settings, which are the starting point for the following
tests.
Since the SMOR system has a large number of settings, an exhaustive list of all the settings necessary for
each test is not given here. The specific settings required for each test are indicated, and it can be supposed
that the other settings do not affect the test in question. For example, when testing the Overcurrent function,
the recloser and the directional control functions, etc, are disabled.
6.8. INPUTS
6.8.1. DIGITAL INPUTS
•
Apply the nominal voltage in order to each of the inputs (CC1 to CC6) and, for models with expansion
board, (CC1 to CC12).
•
Each test checks that the corresponding input is activated and that the remaining inputs (to which no
voltage is applied) are not activated. Use a PC and the GE_LOCAL software to easily check which inputs
get active.
•
Repeat this test at minimum and maximum voltage
6.8.2. SYNCHRONIZATION INPUT IRIG-B
•
Connect the output of an IRIG-B unit with decoded output to the IRIG-B input of the SMOR relay. Special
care must be taken when making the connection because the input is polarized.
•
Check that the time measured by the two units is the same.
6.9. OUTPUTS
•
Check that all the outputs are open
•
Set the Failure to open timer to the maximum. Perform an opening command and check that during the
failure to open time the Trip-1 (A11-B11) and Trip-2 (A12-B12) output contacts are closed.
Содержание SMOR-B GEK 105593C
Страница 5: ......
Страница 9: ...GEK 105593C 4 ...
Страница 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Страница 51: ...GEK 105593C 46 ...
Страница 71: ...GEK 105593C 66 ...
Страница 73: ...GEK 105593C 68 ...
Страница 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Страница 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Страница 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Страница 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Страница 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Страница 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Страница 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Страница 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Страница 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Страница 99: ...GEK 105593C 94 FIGURE 11 RS232 CONNECTION SMOR B WITH PC FIGURE 12 RS232 CONNECTION SMOR B WITH MODEM ...
Страница 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Страница 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...