GEK-105593C
10
COLUMN
LED Nº
LEFT
LED
Nº
RIGHT
1
Phase A trip
9
Frequency trip (81)
2
Phase B trip
10
Recloser out of service
3
Phase C trip
11
Reclose in progress
4
Ground trip
12
Recloser in lockout status
5
Timed Overcurrent trip
13
Circuit Breaker Open
6
Instantaneous Overcurrent trip
14
Coil supervision alarm
7
Negative sequence trip
15
Unit alarm
8
Voltage trip (27/59/59N)
16
Remote communication mode
2.2.4. SUPERVISION OF TRIP AND CLOSING CIRCUITS
On the optional expansion board there are two complete supervision circuits for the trip and/or closing coil of
the breaker (one input for each coil). These supervision inputs monitor both the battery voltage and the
continuity of the tripping or closing circuits, monitoring the flow of a small current injected into the circuit.
The unit independently identifies in the event recorder and states matrix the continuity of each coil ("coil
continuity alarm") and the loss of voltage to command the breaker ("coil DC supply alarm.")
Circuit supervision is carried out on a permanent basis, regardless of whether the breaker is in the open or
closed status, since the supervision circuit is connected both to contact 52/a and 52/b of the breaker. For the
supervision to be carried out correctly, the supervision circuits must be connected to the tripping or closing
coils as shown in the following diagrams:
TRIP CIRCUIT SUPERVISION
Содержание SMOR-B GEK 105593C
Страница 5: ......
Страница 9: ...GEK 105593C 4 ...
Страница 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Страница 51: ...GEK 105593C 46 ...
Страница 71: ...GEK 105593C 66 ...
Страница 73: ...GEK 105593C 68 ...
Страница 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Страница 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Страница 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Страница 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Страница 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Страница 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Страница 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Страница 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Страница 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Страница 99: ...GEK 105593C 94 FIGURE 11 RS232 CONNECTION SMOR B WITH PC FIGURE 12 RS232 CONNECTION SMOR B WITH MODEM ...
Страница 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Страница 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...