6.2. VISUAL INSPECTION
Check that the relay has not suffered any kind of damage due to transport and handling.
Check that all the screws are sufficiently tight and that the terminal strips have not been damaged in any
way.
Check that the information on the characteristics plate coincide with those of the ordered model.
6.3. INSULATION TESTS
Progressively apply 2000 rms volts for the initial test across all the short-circuited terminals of a group and
the case, for one second.
During the tests A9 and B9 terminals must be grounded for safety reasons
The independent groups on the relay are as follows:
Group 1:
A10,B10
Power supply
Group 2:
A5 to A8, B5 to B8
Voltage transformers
Group 3:
A1 to A4, B1 to B4
Current transformers
Group 4:
C9, C10, D9, D10
Inputs group 1
C11,C12, D11, D12
Inputs group 2
Group 5:
A11, B11
Trip 1
Group 6:
A12, B12
Trip 2
Group 7:
C1, D1
Reclose 1
Group 8
C2, D2
Reclose 2
Group 9
C3, D3
Unit alarm
Group 10:
C4 to C6, D4 and D5
Outputs Group 1 (outputs 1 to 4)
Group 11:
C7, C8, D6 to D8
Outputs Group 2 (outputs 5 to 8)
For models with expansion board, add the following groups:
Group 12:
E9, E10, F9 and F10
Inputs Group 3
E11,E12,F11 and F12
Inputs Group 4
Group 13
E5, E6, F5 and F6
Coil 1 and 2 supervision
E7, E8, F7 and F8
Group 14:
E1, F1
Output 9
Group 15:
E2, F2
Output 10
Group 16:
E3, F3
Output 11
Group 17:
E4, F4
Output 12
Содержание SMOR-B GEK 105593C
Страница 5: ......
Страница 9: ...GEK 105593C 4 ...
Страница 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Страница 51: ...GEK 105593C 46 ...
Страница 71: ...GEK 105593C 66 ...
Страница 73: ...GEK 105593C 68 ...
Страница 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Страница 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Страница 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Страница 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Страница 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Страница 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Страница 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Страница 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Страница 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Страница 99: ...GEK 105593C 94 FIGURE 11 RS232 CONNECTION SMOR B WITH PC FIGURE 12 RS232 CONNECTION SMOR B WITH MODEM ...
Страница 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Страница 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...