background image

Modifications reserved 

Page 46/79 

OPM_SGS_USM_M22_M30_2US_V010.doc 

User Manual 

SG Series 225 & 300 UL S2

 

 

NOTE ! 

During the first commissioning 

SG Series 225 & 300

 requests a set up of the UPS 

configuration parameters presented in the following screens. 
 
Without such configuration it is not possible to continue with the commissioning 
procedure. 

 
 

 

WARNING ! 

The setup of the UPS configuration parameters must be done only 

by a GE GLOBAL SERVICES FIELD ENGINEER. 
The setup of mistaken values could compromise the integrity and 
reliability of the UPS.

 

 
 
In this mode the keys perform the following functions: 
 

 

 

Confirm the selection made and select the next parameter. 

 

ESC

 

 

Re-establish default value. 

 

 

 

Modify or insert the selected value. 

 

 

 

Save the configuration of set parameters. 

 
 
 

`

Configuration 

DISPLAY CONFIGURATION 

 
 

 

Select language 

ENGLISH

   

 

 

 

 

ESC 

 

 

 

DISPLAY CONFIGURATION screen 

 

Select language 

This parameter allows the choice of language used to display 

the information. 

 

Pushing the pushbuttons 

“1

st

 button” (METER)

 and 

“2

nd

 button” 

(ALARM)

 together automatically sets the 

LCD

 communication for 

“ENGLISH”. 

 
 

`

Configuration 

UPS CONFIGURATION 

 

Input frequency 

60 

Hz 

Output frequency 

60  Hz 

Inverter voltage 

277 

 

 
 

 

ESC 

 

 

 

 

UPS CONFIGURATION screen 

 

Input frequency 

Rectifier input frequency value. 
The default value is 60Hz and shall not be changed. 

 

Output frequency 

Inverter output frequency value. 

The default value is 60Hz and shall not be changed. 

 

Inverter voltage 

Output voltage PHASE/NEUTRAL of the inverter (default 277V).

 

 

Continue 

 

Содержание SG 225

Страница 1: ...Uninterruptible Power supply SG Series 225 300 225 300 kVA 480Vac UL S2 GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52...

Страница 2: ...ion contained in this publication is intended solely for the purposes indicated The present publication and any other documentation supplied with the UPS system is not to be reproduced either in part...

Страница 3: ...information and describes all you need to know about the use of the UPS Thank you for choosing GE START UP AND COMMISSIONING A GE Global Services Field Engineer must perform start up and commissioning...

Страница 4: ...sses or damages resulting from the use of the information contained in this document WARNING SG Series 225 300 is a product that needs to be installed by a licensed and knowledgeable contractor We rec...

Страница 5: ...4 3 4 Synchronization 17 4 3 5 Load sharing 17 4 4 RECTIFIERS PARALLELED ON THE SAME BATTERY 18 4 5 RECYCLING AT THE END OF SERVICE LIFE 19 5 CONTROL PANEL 20 5 1 CONTROL PANEL 20 5 2 TABLE OF FUNCTI...

Страница 6: ...connect a UPS unit to a Parallel System 67 7 2 6 Complete Parallel System shutdown 69 7 2 7 Restore to normal operation after Load Off 71 7 2 8 Restore to normal operation after EPO Emergency Power Of...

Страница 7: ...ssembling are correctly reattached This UPS is intended for use in a controlled indoor environment free of conductive contaminants and protected against animals intrusion WARNING HIGH EARTH LEAKAGE CU...

Страница 8: ...attery cabinet 2 Tools must have insulated handles and must be insulated so that they will not short battery terminals Do not allow a tool to short between individual or separate battery terminals or...

Страница 9: ...llowing symbols are defined WARNING if instruction is not followed injury or serious equipment damage may occur CAUTION internal parts have dangerous voltage present Risk of electric shock PE Earth GN...

Страница 10: ...6 18 21 10 22 11 Fig 2 1 2 SG Series 225 300 general view with open doors 0 OFF Q2 I ON Q1 I ON 0 OFF SGS_225 300_S2_Switches Q1 Q2_01 Fig 2 1 3 Manual operated switches Fig 2 1 4 Control panel P4 Cus...

Страница 11: ...ther UPS in the market With today s trend toward power factor corrected loads SG Series 225 300 can support more total Load than any other UPS available allowing you to support a greater number of tod...

Страница 12: ...converts the DC voltage into a three phase AC voltage with constant amplitude and frequency which is completely independent and isolated from the AC input voltage Automatic Bypass The Automatic Bypas...

Страница 13: ...ration Mode is selected and the Utility Power is available the Load is normally powered through the Automatic Bypass When the Utility Voltage is detected out of the prescribed tolerances the Load is a...

Страница 14: ...4 3 When a Battery low warning occurs on a unit not necessary to support the present load this unit will shut down after a timeout period selectable The Load is shared between the other units As the w...

Страница 15: ...arm condition will be initiated A Manual Bypass operator initiated will not be considered as an alarm condition Fig 4 2 5 1 Block diagram Automatic Bypass In case of parallel operation Each unit has i...

Страница 16: ...pacity Several units can be paralleled in order to achieve output power greater than the maximum power of a single unit The maximum total power shared between the paralleled units is equal to the tota...

Страница 17: ...own function and operational status and communicates with all other modules in order to act or react if necessary adapting it to the new conditions 4 3 4 Synchronization All units are identical but on...

Страница 18: ...e prepared in advance before the installation The installation must be performed only with the UPS system must be completely shut down The AC Rectifiers input power 5 must be the same with clockwise p...

Страница 19: ...rules It does not contain CFCs chlorofluorocarbons or HCFCs hydrochlorofluorocarbons RECYCLING AT THE END OF SERVICE LIFE GE in compliance with environment protection recommends to the User that the U...

Страница 20: ...ront door acts as the UPS user interface and comprises of the following elements Back lit Graphic Display LCD with the following characteristics Multilanguage communication interface English German It...

Страница 21: ...NOTE Inverter OFF command is disabled when eBoost Operation Mode is enabled Key Load Off The key Load Off is protected by a transparent cover By pressing it you immediately separate the UPS from the...

Страница 22: ...D is also lit when the load is not protected by UPS or in case Q1 is open LED Operation green color When lit indicates that the UPS is functioning correctly and the load is system protected Load suppl...

Страница 23: ...s to specific requirements and to view UPS identification data See Section 6 4 CMDS COMMANDS Allows the user to execute UPS operation commands See Section 6 5 The LCD screen after 5 minutes of inactiv...

Страница 24: ...vel between 26 and 50 LED A B Indicate a load level between 51 and 75 LED A B C Indicate a load level between 76 and 100 LED A B C D Indicate a load level between 101 and 124 LED D blinking Indicates...

Страница 25: ...Min Battery data screen V The battery voltage I The battery current negative values correspond to the discharge of the battery T The temperature of the battery SENSOR DISABLE indicates sensor disabled...

Страница 26: ...Q2 close LOAD ON INVERTER Q1 OPEN LOAD ON BYPASS LOAD OFF LOAD ON BYPASS eBoost ON BATTERY Home Meter SYSTEM LOAD L1 44 8 kW 49 8 kVA PF 0 90 L2 35 8 kW 39 8 kVA PF 0 90 L3 26 9 kW 29 9 kVA PF 0 90 LO...

Страница 27: ...hours This counter is displayed only when eBoost Operation Mode is available option Home Meter BATTERY DISCHARGE COUNTERS Residual Charge Level 100 81 81 51 50 21 20 0 15 7 3 1 On Battery Time h 15 St...

Страница 28: ...an 3 seconds The events displayed are the standard GE events as described in the Section 6 3 1 EVENTS Alarms and Messages Home Alarm ALARM LEVEL 1 USER LEVEL 2 SERVICE V Alarms screen LEVEL 1 USER Chr...

Страница 29: ...FAILURE The parallel communication bus system is subject to high errors rate on channel JA 4007 BUS JB CRC FAILURE The parallel communication bus system is subject to high errors rate on channel JB 40...

Страница 30: ...urrent limiting mode Decrease the load to stabilize DC Bus 4130 TURN ON RECT OR SHUTDOWN UPS Rectifier and Inverter are OFF The DC Power Supply is discharging the Battery Rectifier must be restarted o...

Страница 31: ...c Bypass 4405 K6 OPENING FAILURE K6 closed despite an opening command being issued Signaled by auxiliary contact 4406 SSM FAILURE A faulty current has been detected in the static switch causing the op...

Страница 32: ...ivated by Service Center 4698 BATTERY POWER INSUFFICIENT In case of Utility Failure with the actual Load the run time would be below stop operation time default 3 minutes 4700 DC LOW Battery voltage i...

Страница 33: ...1 RECTIFIER ON Rectifier started 4162 RECTIFIER OFF Rectifier shutdown 4163 GENERATOR ON Customer Interface Board X1 11 22 received a Gen set ON signal Operating mode depend on setting of Parameters 4...

Страница 34: ...o synchronize with Utility 4583 COMMAND TO SYNCHRONIZE Command to synchronize with Utility 4600 COMMAND UPS ON The eBoost Operation Mode has been disabled or the programmed time is expired The UPS ret...

Страница 35: ...below 10 or above 80 Test is postponed for 1 week 4763 REMOTE CONTROL ON Inverter can be started or shutdown by remote control Commands source can be chosen depending on the value of parameter Servic...

Страница 36: ...__ __ Series No UPS rating kVA Customer Place Date Sent by 1 Record the exact UPS status on the panel when the failure appeared 2 On the LCD panel enter the alarms mode and record the alarms messages...

Страница 37: ...set or modify the parameters ESC Allows to exit a selected screen without making any modification U Scrolls backward to the previous line V Scrolls forward to the next line Allows to access a value t...

Страница 38: ...Y N the remote control through modem calls by using this parameter For modem connection the default setting is for serial port J3 on Customer Interface Init This parameter presents the modem initiali...

Страница 39: ...ols the baud rate used for data transmission Parity This parameter controls the parity used for data transmission Odd O even E and No Parity NO can be selected In case No Parity NO has been set automa...

Страница 40: ...the week the Y N parameter is automatically disabled if this condition is not satisfied In case this minimum time in VFI Operation Mode is not respected the eBoost Operation Mode will be disabled If t...

Страница 41: ...n Mode during the night and week end If the eBoost Operation Mode must be enabled all nights d3 Monday d7 Friday between 18 00 in the evening and 06 00 of the following morning and during all Saturday...

Страница 42: ...of weekday d3 Monday has no effect as it is followed by the eBoost STOP time of weekday d4 Tuesday It can be without change of meaning any time between 18 00 and 23 59 Similarly the eBoost Operation...

Страница 43: ...INVERTER ON Command to switch the inverter INVERTER OFF Command to shutdown the inverter RECTIFIER ON Command to switch the rectifier Only for Service Center the command access is protected by a code...

Страница 44: ...tility to the UPS Open only the front door do not remove any panels Check after every step for correct reaction of the UPS LED s on the panel and correct voltage and current measurements before you pr...

Страница 45: ...Rectifier OK LED 2 Utility Bypass OK LED 3 Rectifier ON LED 4a Discharging Battery LED 4b Charging Battery LED 5 Inverter available LED 6 Inverter ON LED 7 Q1 closed LED 8 Automatic Bypass ON LED 9 Ma...

Страница 46: ...rameter ESC Re establish default value Modify or insert the selected value Save the configuration of set parameters Configuration DISPLAY CONFIGURATION Select language ENGLISH ESC DISPLAY CONFIGURATIO...

Страница 47: ...t charge 2 23Vdc for cell 240 cells x 2 23Vdc 535Vdc Open battery with boost charge 2 23 2 35 boost charge Vdc for cell 232 cells x 2 23Vdc 518 545 Vdc Recharge current Maximum battery recharge curren...

Страница 48: ...the Inverter by pressing the Inverter ON I key Soft start of Inverter indicated with blinking LED 5 Inverter available At the end of Soft start the LED 5 Inverter available remains lit Automatic trans...

Страница 49: ...rter supplying the Load the UPS Output Switch Q1 is closed Pos I and the Manual Bypass Switch Q2 option is open Pos O The External Battery Switch or Fuses are closed Pos I The Synoptic Diagram must di...

Страница 50: ...ned Press the MUTE key to reset the alarm buzzer The Synoptic Diagram must display the status LOAD SUPPLIED BY MANUAL BYPASS Q2 4 Disconnect the Battery from the UPS by opening Pos O the External Batt...

Страница 51: ...ass Q2 option 1 If not already supplied separate Utility Inputs switch ON the Utility power to the Rectifier input 2 Close the UPS Output Switch Q1 Pos I Load is now supplied parallel through Automati...

Страница 52: ...rns OFF The Synoptic Diagram must display the status LOAD SUPPLIED BY AUTOMATIC BYPASS 5 Insert the Inverter by pressing the Inverter ON I key Soft start of Inverter indicated with blinking LED 5 Inve...

Страница 53: ...S Rectifier and Inverter are shut down all output and input Contactors will be opened LED 3 Rectifier ON LED 5 Inverter available and LED 10 Load on UPS are OFF LED Alarm is lit and the LED Operation...

Страница 54: ...mmands COMMANDS RESET TOTAL OFF REQUEST LOAD OFF V 1 Reset Load Off Restore the command Load Off by entering the screen COMMANDS RESET TOTAL OFF The Load is supplied by the Utility through the Automat...

Страница 55: ...s lit 1 Reset the EPO Emergency Power Off button Press the MUTE key to reset alarm and acoustical alarm LED Alarm remains lit 2 Press the Inverter OFF O key Load is transferred to Utility by Automatic...

Страница 56: ...switch option LED 1 Utility Rectifier OK LED 2 Utility Bypass OK LED 3 Rectifier ON LED 4a Discharging Battery LED 4b Charging Battery LED 5 Inverter available LED 6 Inverter ON LED 7 Q1 closed LED 8...

Страница 57: ...rameter ESC Re establish default value Modify or insert the selected value Save the configuration of set parameters Configuration DISPLAY CONFIGURATION Select language ENGLISH ESC DISPLAY CONFIGURATIO...

Страница 58: ...t charge 2 23Vdc for cell 240 cells x 2 23Vdc 535Vdc Open battery with boost charge 2 23 2 35 boost charge Vdc for cell 232 cells x 2 23Vdc 518 545 Vdc Recharge current Maximum battery recharge curren...

Страница 59: ...LED 3 Rectifier ON must remain lit thus indicating that the DC Link has reached floating voltage 540Vdc 4 Repeat the procedures 2 and 3 for each next Unit When closing UPS output switch Q1 on the last...

Страница 60: ...tic Diagram of first unit Synoptic Diagram of other units 7 Load supply SG Series 225 300 Parallel System is now running supplying power to the output Insert the Loads one by one to the output of the...

Страница 61: ...e Manual Bypass Switches Q2 option are open Pos O The External Battery Switch or Fuses are closed Pos I The Synoptic Diagram on all UPS units must display the status LOAD SUPPLIED BY INVERTER 1 Discon...

Страница 62: ...Contactors are opened The Synoptic Diagram on all UPS units must display the status LOAD SUPPLIED BY MANUAL BYPASS Q2 Synoptic Diagram of first unit Synoptic Diagram of other units 4 Disconnect the B...

Страница 63: ...m are lit Initial status Load supplied from all Manual Bypass Q2 of the Parallel System All Manual Bypass Switches Q2 of the Parallel System are closed 1 If not already supplied separate utility input...

Страница 64: ...agram of other units 6 Insert the Inverter by pressing the Inverter ON I key on first unit Soft start of Inverter indicated with blinking LED 5 Inverter available At the end of Soft start the LED 5 In...

Страница 65: ...Redundant Parallel System 1 Disconnect the Inverter by pressing the Inverter OFF O key and hold until the LED 5 Inverter available turns OFF on the Unit to separate With redundant system pressing the...

Страница 66: ...parate Synoptic Diagram of other units 4 Disconnect the Battery on the Unit to separate by opening Pos O the External Battery Switch or Fuses Wait 5 minutes for DC Link Capacitors discharge 5 Disconne...

Страница 67: ...rectly The protection panels are fastened in their correct position The UPS Output Switch Q1 Manual Bypass Switch Q2 option and the External Battery Switch or Fuses must be open Pos O 1 Switch ON the...

Страница 68: ...ration the LED 3 Rectifier ON must remain lit thus indicating that the DC Link has reached floating voltage 540Vdc 4 Insert the Inverter by pressing the Inverter ON I key on the Unit to reconnect The...

Страница 69: ...ng the Load the UPS Output Switches Q1 and the External Battery Switch or Fuses are closed Pos I and the Manual Bypass Switches Q2 option are open Pos O Initial status Load supplied from all Inverters...

Страница 70: ...l Battery Switch or Fuses Wait 5 minutes for DC Link Capacitors discharge 4 Disconnect the Utility supply on all Units Complete power shutdown will OFF the LCD Display Panel Synoptic Diagram of first...

Страница 71: ...its after pressing the Load Off key All Contactors are open Rectifier Inverter and Static Switch shutdown LED Alarm is lit Home Commands COMMANDS RESET TOTAL OFF REQUEST TOTAL OFF V 1 Reset Load Off o...

Страница 72: ...iagram of other units 3 Insert the Inverter by pressing the Inverter ON I key on all other units Do not start the next Inverter until the sequence of the previous ends Soft start of Inverter indicated...

Страница 73: ...fter activation of EPO Emergency Power Off with Utility available All Contactors are open Rectifier Inverter and Static Switch shutdown LED Alarm is lit 1 Reset the EPO Emergency Power Off button Pres...

Страница 74: ...sert the Inverter by pressing the Inverter ON I key on all other units Do not start the next Inverter until the sequence of the previous ends Soft start of Inverter indicated with blinking LED 5 Inver...

Страница 75: ...ke timely decisions in case of changing critical conditions With comprehensive data collection and analysis IRIS is not only a remote monitoring diagnostics RM D system but the core of the integrated...

Страница 76: ...at one end with a D female plug 25 pin J2 P4 Customer Interface Board NOTE The alarms on free potential contacts can be connected on terminals X1 instead J2 see correlation X1 J2 in Section 4 1 of th...

Страница 77: ...ng during normal operation the unit has not been serviced for the last 20 000 hours by a GE trained technician We highly recommend that you contact your Service Center for preventive maintenance work...

Страница 78: ...at least 12 hours every 3 months If not the Battery may be permanently damaged 9 1 6 UPS room conditions and temperature The UPS room and the Battery Room have to be maintained clean and free from dus...

Страница 79: ...User Manual SG Series 225 300 UL S2 10 NOTES 10 1 NOTES FORM It is recommended to note in this section Notes with date and short description all the operations performed on the UPS as maintenance comp...

Отзывы: