![GE SG 225 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/ge/sg-225/sg-225_user-manual_4168088041.webp)
Modifications reserved
Page 41/79
OPM_SGS_USM_M22_M30_2US_V010.doc
User Manual
SG Series 225 & 300 UL S2
To better understand the
eBoost™
programming modes, some typical examples are shown:
Example 1
:
For continuous
eBoost™ Operation Mode
set the
eBoost START
times to 00:00
and the
eBoost STOP
times to 23:59
for all weekdays, but almost
1 day must have 1 minute of
VFI
programmation: i.e
d2 -
Sunday
00:00 to 23:58).
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
eBoost START
00:00 00:00 00:00 00:00 00:00 00:00 00:00
eBoost STOP
23:59 23:58 23:59 23:59 23:59 23:59 23:59
Example 2
:
eBoost STOP
before
eBoost START
.
eBoost START
18:00,
eBoost STOP
06:00 for weekday
d4 - Tuesday
.
Means that on
d4 - Tuesday
the
eBoost™ Operation Mode
is active between 00:00 and 06:00 and
between 18:00 and 23:59.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
eBoost START
00:00 00:00 00:00 18:00 00:00 00:00 00:00
eBoost STOP
23:59 23:59 23:59 06:00 23:59 23:59 23:59
Example 3
:
eBoost™ Operation Mode
during the night and week-end.
If the
eBoost™ Operation Mode
must be enabled all nights (
d3 - Monday
÷
d7 - Friday
) between 18:00 in
the evening and 06:00 of the following morning and during all Saturday (
d1
) and Sunday (
d2
), the
corresponding parameters are:
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
eBoost START
00:00 00:00 18:00 18:00 18:00 18:00 18:00
eBoost STOP
23:59 23:59 06:00 06:00 06:00 06:00 06:00
Example 4
:
If the
eBoost™ Operation Mode
must be enabled on
Monday
(
d3
)
and
Tuesday
(
d4
)
between 18:00 in the
evening and 06:00 of the following morning, on
Friday
(
d7
)
between 12:00 and 13:00, during all
Saturday
(
d1
)
and on
Sunday
(
d2
)
until 20:00, the corresponding parameters are.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
eBoost START
00:00 00:00 18:00 18:00 00:00 00:00 12:00
eBoost STOP
23:59 20:00 23:59 06:00 06:00 00:00 13:00
eBoost START
eBoost STOP
In dark color are displayed the times with
eBoost™ Operation Mode
.
The arrows indicate the conditions given by the
eBoost START
and
eBoost STOP
times introduced with
the parameters.
Note that on day
d6 - Thursday
the interval has length 0 (zero), therefore the
eBoost™ Operation Mode