SecoGear Medium-voltage Switchgear Application and Technical Guide
DET-882
Ground and Test Device
66
©2017 General Electric All Rights Reserved
SECTION 7.
GROUND AND TEST DEVICE
An optional Manual Ground and Test Device, designed to
meet ANSI, IEEE, and NEMA standards, is available for 1200 A
or 2000 A. Consider the current rating and the short-circuit
rating of the metal-clad unit when selecting a device for
your equipment.
The Manual Ground and Test Device is an auxiliary
removable device for use in SecoGear Metal-clad switchgear
equipment during initial installation and at normal
maintenance periods. The function of this device is to solidly
ground the equipment manually as well as permit various
types of tests.
Exposed Ground and Test Device terminals can also be used
for applying high-potential tests, measuring insulation
resistance to ground, and phasing out cables. The device
does not have interrupters or a mechanism; therefore, it has
no interrupting or closing capability.
SAFETY
The Ground and Test Device is often used during initial
installation and for troubleshooting when the possibility of
making an error is greatest.
The Ground and Test Device and the metal-clad switchgear
have interlocks to prevent unsafe operation. Unfortunately, it
is not possible to eliminate every hazard with interlocks;
therefore, is the responsibility of the person using this device
to recognize the potential hazards while working on
potentially energized equipment and take adequate
precautions.
Interlocks are provided for the safety of the operator and
correct operation of the device. If an interlock does not
function as described in the Ground and Test Device manual
(DEH-50007), do not make any adjustment or force the
device into position.
Figure 7-1: Device, Front View
Figure 7-2: Device, Contact Arms
Table 7-1: SecoVac VB2+ Vacuum Circuit Breaker
Characteristics
SKU
Description
Assembly No.
SVGT10
IEEE G&T Device 1200 A/31.5 kA
Manual
3PVB069044
SVGT20
IEEE G&T Device 1200 A/40 kA
Manual
3PVB069045
SVGT30
IEEE G&T Device 2000 A/40 kA
Manual
3PVB069046