background image

3.6

FTP Server

The FTP server included with the QuickPanel

+

supports standard (RFC 959). It does not

support SFTP or implicit FTPS, which uses different ports and is based on SSH rather
than SSL.

The FTP server is configured with the Quick Panel+ Setup Tool. By default, the server is
not enabled. Once enabled, a background program will run, waiting for clients to connect.
Up to ten connections are supported. Sessions that are idle for five minutes are terminated
by the server.

The server supports non-secure operation. All information including username, password,
and data is transmitted with no encryption and susceptible to packet sniffing and various
FTP attacks.

Note

If the server status is changed, the QuickPanel

+

must be re-booted before changes

take effect.

3.6.1

Authentication of Remote Users

The FTP root directory is
available from the QuickPanel

+

as \ and is the root of the

flash device.

The server only supports anonymous login: Anonymous with password requested (but not
validated). This may prevent some types of attacks and is required by some clients. Once
connected, a remote user is logged into the FTP root directory.

3.6.2

FTP with Removable Flash Devices

All removable flash devices appear to remote FTP users as directories off the FTP root
directory. Computer Flash card partitions display as directories such as

\SDMemory

and

USB Flash Keys as directories such as

\Hard Disk

. Full access privileges are granted for

the client in these folders/devices.

Removable flash device directories are captured when a session is opened and are not
changed while the session exists. If you start without an SD Card installed, you will have
to close your session and login again to see the SD Card directory. If the SD Card existed
when you logged in and is removed and inserted, it will still work, provided the SD
Card’s device name did not change during reinsertion.

24

GFK-2847F

Qui Operator Interface User Manual

For public disclosure

Содержание QuickPanel+

Страница 1: ...GE Intelligent Platforms GFK 2847F QuickPanel Operator Interface IC755CxW07CDx 7 Display IC755CxS10CDx 10 Display IC755CxS12CDx 12 Display IC755CxS15CDx 15 Display User Manual For public disclosure ...

Страница 2: ... pending patent applications covering subject matter in this document The furnishing of this document does not provide any license whatsoever to any of these patents GE provides the following document and the information included therein as is and without warranty of any kind expressed or implied including but not limited to any implied statutory warranty of merchantability or fitness for particul...

Страница 3: ...result in personal injury or death Caution Indicates a procedure condition or statement that if not strictly observed could result in damage to or destruction of equipment Attention Indicates a procedure condition or statement that should be strictly followed to improve these applications For public disclosure ...

Страница 4: ...support ip ge com Customer Care Email customercare ip ge com Primary language of support English Europe the Middle East and Africa Online Technical Support http support ge ip com Phone 800 1 433 2682 EMEA Direct Dial 420 23 901 5850 if toll free 800 option is unavailable or dialing from a mobile telephone Technical Support Email support emea ip ge com Customer Care Email customercare emea ip ge co...

Страница 5: ...g Project to SD Card 22 3 5 Updating a Machine Edition Project 23 3 6 FTP Server 24 3 6 1 Authentication of Remote Users 24 3 6 2 FTP with Removable Flash Devices 24 3 7 HTTP Server 25 3 8 SNTP Server 25 4 Installation 27 4 1 Installing the Protective Sheet 27 4 2 Choosing a Mounting Location 28 4 3 Panel Mounting 29 4 4 Installation Procedure 31 4 5 Mounting on a VESA Arm 33 4 6 Installing and Re...

Страница 6: ...g the Touchscreen 48 5 2 Keyboard 49 5 2 1 External Keyboard Optional 49 5 2 2 Soft Input Panel 49 5 3 Mouse 49 5 4 Memory 50 5 4 1 Dynamic RAM Memory 50 5 4 2 Modifying Memory Allocation 51 Appendix A Product Certifications and Installation Guidelines 53 Appendix B Orderable Part Numbers 55 Appendix C IC755CxS12CDA Serial Port Details 57 Index 59 6 GFK 2847F QuickPanel Operator Interface User Man...

Страница 7: ...pecifications Item IC755CxW07CDx IC755CxS10CDx IC755CxS12CDx IC755CxS15CDx Processor Freescale i MX535 1 GHz ARM Cortex A8 Memory RAM DDR2 SDRAM 512 MB DDR3 SDRAM 1 GB ROM SLC NAND 256 MB SLC NAND 512 MB SRAM 512 KB with battery backup Operating System Microsoft Windows Embedded Compact 7 Display Type 7 Widescreen TFT LCD 10 4 Standard TFT LCD 12 1 Standard TFT LCD 15 Standard TFT LCD Resolution 8...

Страница 8: ... GND internally 1 1 2 Physical Specifications and Mounting Options Item IC755CxW07CDx IC755CxS10CDx IC755CxS12CDx IC755CxS15CDx Dimensions L W D 192 137 36 mm 7 56 5 39 1 42 in 278 222 65 mm 10 95 8 74 2 56 in 314 248 65 mm 12 36 9 76 2 56 in 399 323 70 mm 15 71 12 72 2 76 in Weight 0 80 kg 1 76 lbs 2 40 kg 5 29 lbs 3 kg 6 61 lbs 4 46 kg 9 83 lbs Mounting Options Panel cutout dimensions 183 50 128...

Страница 9: ...Storage Temperature 10 to 60 C 14 to 140 F Ambient Humidity Operating and Storage 85 RH Non condensing wet bulb temperature 30 C 86 F or less Environment Pollution Degree 2 Indoor use only Vibration Resistance 5 to 9 Hz single amplitude 3 5 mm 9 to 150 Hz constant accelerated velocity 9 8 m s2 X Y Z directions 10 time 100 minutes Compliance 3502 IEC61131 2 JIS B Altitude 800 1114 hPa altitude up t...

Страница 10: ... Overview The following diagrams display the physical layout of the QuickPanel including locations of status LEDs communications ports and connectors Battery Cover COM USB Host Ports LAN Input Power SD Card MICRO USB LINE OUT MIC IN Status Indicator LED Touchscreen LCD IC755CxW07CDx Hardware Features 10 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 11: ...Status Indicator LED Touchscreen LCD SD Card USB Host Ports MICRO USB LAN2 COM1 LAN1 Input Power LINE OUT COM2 IC755CxS10CDx Hardware Features Introduction GFK 2847F User Manual 11 For public disclosure ...

Страница 12: ... IC755CxS12CDx Hardware Features 12 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 13: ...Touchscreen LCD Status Indicator LED SD Card Input Power LINE OUT USB Host Ports MICRO USB COM2 LAN2 COM1 LAN1 IC755CxS15CDx Hardware Features Introduction GFK 2847F User Manual 13 For public disclosure ...

Страница 14: ...m starting Green solid Normal operating state Green blinking Backlight off Red blinking Backlight failure Off Power not applied to the unit 1 2 2 2 Ethernet Port LED Operation The Ethernet port has two LED indicators Speed and Link Activity Speed Link Activity LED LED State Operating State Speed On Yellow 10 100 Link Activity On Green Link status 14 GFK 2847F QuickPanel Operator Interface User Man...

Страница 15: ...ate should such action be necessary For phone numbers and email addresses refer to the section Contact Information After unpacking the unit record all serial numbers Serial numbers are required if you need to contact Customer Care during the warranty period Shipping containers and packing material should be saved in case it is necessary to transport or ship the unit Verify that all system componen...

Страница 16: ...wer Connector Qty 1 Mounting Brackets Qty 4 Protective Sheet Qty 1 not shown Gasket Qty 1 not shown pre installed QuickPanel Operator Interface IC755CxW07CDx Example Package Contents 16 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 17: ...ICAL SHOCK HAZARD To avoid personal injury or damage to equipment ensure that the dc supply is disconnected from power and that the leads are not energized before attaching them to the unit s power supply plug Warning If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired Power Supply Optional Ethernet Connection Optional US...

Страница 18: ...wer cable is not energized 2 Loosen the screw clamps on the mating power connector 3 Strip the insulation from the power cables 4 Secure the power cable to the mating connector noting polarity and tighten the screw clamps The torque for the attaching screws is 0 3 Nm 2 66 in lb 5 Apply dc power to the unit During normal startup and operation the QuickPanel status LED indicator displays as follows ...

Страница 19: ...rom the Control Panel double tap Network and Dial up Connectionsto configure network settings 5 Run the Backup Utility to save the settings 2 4 Runtime Setup To download an application to a QuickPanel Operator Interface set up a data link between the unit and your development workstation Refer to the section Ethernet for IC755CxW07CDx and IC755CxSxxCDx and the Proficy Machine Edition PME online he...

Страница 20: ...uickPanel To shut down the QuickPanel 1 Quit any programs that are running and wait for all file operations to complete 2 If you have not changed operating system settings for example brightness or touchscreen sensitivity or do not want to save the changes remove ac power from the dc supply 3 To save changes to operating system settings run Backup When the Backup dialog box displays Completed Succ...

Страница 21: ...ace The Backup Utility saves the changes made to the Windows Registry or Desktop to Flash Memory This is required because the QuickPanel is not battery powered Specifically the Backup Utility achieves the following Stores the Windows Embedded Compact 7 registry including any control panel settings in Flash memory Stores any changes or additions made to the Windows sub tree of the file system in th...

Страница 22: ...D card port 2 Double tap the Copy Project to SD Card icon on the desktop 3 Tap Yes when the Copy Project Query confirmation dialog box appears Caution Copying a project while the Proficy Machine Edition runtimes are active may cause an incomplete copy to be created if the runtimes are also writing to files in the project folders The utility can detect this situation and will notify you to stop the...

Страница 23: ... update If there is more than one flash device with a valid project copy present a Select Media confirmation dialog displays allowing you to choose which flash device to update with Select the device from the list and select OK to continue When a valid project is found on the flash device you will be prompted to install the project or skip it Tap OK to install or Cancel to skip the install and con...

Страница 24: ...t of the flash device The server only supports anonymous login Anonymous with password requested but not validated This may prevent some types of attacks and is required by some clients Once connected a remote user is logged into the FTP root directory 3 6 2 FTP with Removable Flash Devices All removable flash devices appear to remote FTP users as directories off the FTP root directory Computer Fl...

Страница 25: ...on Note If the server status is changed the QuickPanel must be re booted before changes take effect 3 8 SNTP Server The SNTP server included with the QuickPanel supports SNTP Version 4 for IPv4 IPv6 and OSI The SNTP server is configured with the Quick Panel Setup Tool By default the server is not enabled Once enabled the server will refresh the time specified in the setup tool configuration Pressi...

Страница 26: ...Notes 26 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 27: ...1 Installing the Protective Sheet To install the protective sheet 1 Remove the protective film on the screen of the QuickPanel 2 Wipe the display of any dust or fingerprints 3 Peel a corner of the clear side of the protective sheet 4 Begin applying the corner to the display 5 Slowly apply the rest of the protective sheet smoothing out as you go 6 Peel the green curing film from the protective shee...

Страница 28: ...to insert and remove the SD card cables and mounting brackets Choose a location that will allow natural convection air flow from bottom to top of the QuickPanel enclosure Do not mount the QuickPanel at an angle more than 30 from the vertical as illustrated in the following figure Mounting Angle 28 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 29: ...d screwdriver Mounting brackets supplied The IC755CxW07CDx IC755CxS10CDx and IC755CxS12CDx mounting holes are located on the top and bottom sides of the unit IC755CxW07CDx Mounting Holes IC755CxS10CDx and IC755CxS12CDx Mounting Holes Installation GFK 2847F User Manual 29 For public disclosure ...

Страница 30: ...The IC755CxS15CDx mounting holes are located on the top bottom and sides of the unit IC755CxS15CDx Mounting Holes 30 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 31: ...rted in the socket Caution When installing the QuickPanel into the panel pay careful attention while handling the unit so it does not drop and damage the unit To install the QuickPanel 1 Cut an opening in the panel according to the specifications in the following figures Note Panel cutout tolerances are 0 50 0 00 mm 0 02 0 00 in Panel Thickness 1 0 to 5 0 mm 0 04 to 0 20 in 128 50 mm 5 06 in 183 5...

Страница 32: ... the mounting hole as displayed in the following figure 5 Tighten the screws on the mounting bracket in a clock wise direction Torque Range for Mounting Clamp Screws Unit Torque Range IC755CxW07CDx 0 3 Nm 2 66 in lb IC755CxS10CDx 0 7 Nm 6 in lb IC755CxS12CDx 1 0 to 1 2 Nm 8 9 to 10 6 in lb IC755CxS15CDx 1 0 to 1 2 Nm 8 9 to 10 6 in lb 32 GFK 2847F QuickPanel Operator Interface User Manual For publ...

Страница 33: ...n the following figures The IC755CxW07CDx mounting holes attach with M4 screws that are 6 mm 0 24 in or less in length The IC755CxSxxCDx mounting holes attach with M4 screws that are 8 mm 0 32 in or less in length Torque Range for Mounting M4 Screws Unit Torque Range IC755CxW07CDx 0 7 to 0 8 Nm 6 2 to 7 1 in lb IC755CxSxxCDx 1 0 to 1 2 Nm 8 9 to 10 6 in lb 75 mm 75 mm 75 mm 2 95 in 75 mm 2 95 in I...

Страница 34: ...before disposing of batteries Caution 1 Replacing the battery should only be performed by trained personnel and in a non hazardous location 2 If the QuickPanel Operator Interface is VESA mounted detach from the VESA arm when replacing the battery 3 The battery should only be replaced when the unit is powered off 4 Care should be taken to protect and insert the battery with correct polarity 5 Do no...

Страница 35: ...BATT 1 Remove the battery cover by pressing down while sliding outward IC755CxW07CDx Battery Cover Removal 2 Connect the battery harness connector to the header noting keyed orientation Battery Part Number IC755ACCBATT Battery Harness Connection 3 Verify that positive red is down and negative black is up Installation GFK 2847F User Manual 35 For public disclosure ...

Страница 36: ...lowing figure Do not let the harness connector go above the tab Harness Connector Orientation 5 Slide the battery cover into place taking care not to pinch the harness connector 36 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 37: ...CxSxxCDx only with battery part number IC755ACCBATTNL 1 Remove seven screws from the back cover IC755CxSxxCDx Screw Locations Back Cover 2 Gently press on either side tab to release the back cover Side Tab for Cover Release 3 Lift up the back cover to remove Installation GFK 2847F User Manual 37 For public disclosure ...

Страница 38: ...55ACCBATTNL IC755CxSxxCDx Battery 4 Gently remove the coin battery and replace with a new one noting the polarity of the battery 5 Replace the battery cover and tighten all screws to 0 5 Nm 4 4 in lb 38 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 39: ...ection Ethernet Port LED Operation The QuickPanel is equipped with 10BaseT 100 BaseTX Ethernet port s You can connect an Ethernet network cable unshielded twisted pair UTP CAT 5 to the unit through the RJ 45 connector s on the bottom of the enclosure LED indicators on the port indicate channel status The port can be accessed by Windows Embedded Compact 7 network communications or by your applicati...

Страница 40: ...net Mask and Default Gateway if applicable Note Run the Backup utility to save the settings 4 7 3 Serial Port 4 7 3 1 IC755CxW07CDx Serial Port Details A terminal block is supplied The mating terminal block supports stranded 30 14 AWG 0 05 2 00 mm2 wires At a minimum the cable must be rated for 75 C 167 F or more Secure the serial cable to the mating connector while noting signal orientation and t...

Страница 41: ...3 Nm 2 66 in lb Connectors Euro Terminal Tyco Electronics 284539 5 Mating Connectors Tyco Electronics 284510 5 4 7 3 2 1 Serial Port COM1 Interface RS 232 COM1 Pin Details Pin Signal Name Pin out 1 TXD 5 1 2 RXD 3 RTS 4 CTS 5 SGND 4 7 3 2 2 Serial Port COM2 Interface RS 232C 485 default is RS 485 Half duplex COM2 Pin Details Pin RS 232 RS 485 Pin out Signal Name Signal Name Full duplex Signal Name...

Страница 42: ...ing DIP SW Bit ON OFF DIP SW Bit ON OFF SW2 1 OFF SW4 1 ON 2 OFF 2 ON 3 OFF 3 OFF 4 OFF 4 OFF 5 ON 5 ON 6 ON 6 ON 7 OFF 7 OFF 8 ON 8 OFF SW3 1 OFF SW5 1 OFF 2 ON 2 OFF 3 OFF 3 OFF 4 OFF 4 OFF 42 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 43: ...Switch Setting DIPSW Bit ON OFF DIPSW Bit ON OFF SW2 1 OFF SW4 1 ON 2 OFF 2 ON 3 ON 3 ON 4 OFF 4 ON 5 ON 5 ON 6 ON 6 ON 7 OFF 7 OFF 8 ON 8 OFF SW3 1 OFF SW5 1 OFF 2 ON 2 OFF 3 OFF 3 OFF 4 ON 4 OFF Installation GFK 2847F User Manual 43 For public disclosure ...

Страница 44: ... require installation of the custom driver software Interface USB 2 0 Number of Ports Two Connectors Type A connector Maximum Supply Current 0 5 A per port Pin Signal Name Pin out 1 USB_VCC 2 USB_D 3 USB_D 4 USB_GND 4 7 4 2 USB Device Port Details for IC755CxW07CDx and IC755CxSxxCDx The USB device port allows the QuickPanel Operator Interface to be used as Slave device Interface USB 2 0 Number of ...

Страница 45: ...evel 1 Vrms Pin Signal Name Pin out 1 GND 1 2 3 2 Lineout R 3 Lineout L 4 7 6 Audio MIC IN Details only applicable to IC755CxW07CDx Interface MIC IN monaural Number of Ports One Connectors φ3 5 mm jack Maximum output level 250 mVrms Pin Signal Name Pin out 1 GND 1 2 3 2 Lineout R 3 Lineout L Installation GFK 2847F User Manual 45 For public disclosure ...

Страница 46: ...al 4 7 7 1 SD Card Storage Details Connectors SD card slot push in push out method Card support SD SDHC memory card Maximum capacity 32 GB Note During insertion observe the orientation of the SD card as displayed in the following figures IC755CxW07CDx SD Card Location IC755CxSxxCDx SD Card Location 46 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 47: ... could damage the touchscreen display 5 1 1 Adjusting the Display Brightness To adjust the brightness of the display 1 From the Control Panel double tap Display and select the Brightness tab to display the Brightness window 2 Drag the Brightness slider bar between Lowest and Highest 3 Tap OK to exit the control panel 4 Run the Backup Utility to save the settings 5 1 2 Configuring the Backlight To ...

Страница 48: ...nel tab 3 Select Recalibrate Touch Screen 4 Select Recalibrate Touch Sensor Note During IC755CxW07CDx touchscreen sensor re calibration the user is prompted to activate a switch located in the battery compartment This is not applicable to any other panel sizes 5 Remove the battery cover and press the switch Battery Cover Switch Touchscreen Sensor Calibration Switch 6 Replace the battery cover 48 G...

Страница 49: ...nd play 5 2 2 Soft Input Panel The Soft Input Panel SIP is a touchscreen version of a standard keyboard that may be used in place of a standard hardware keyboard An icon in the system tray enables the user to view or hide the SIP To show or hide the SIP from the system tray located on the task bar tap the icon and select Hide Input Panel Note When visible the SIP can be moved around the screen by ...

Страница 50: ... is not retained through a power cycle or reboot The split between program memory and storage memory can be adjusted as necessary to make more room for one or the other depending on your specific application needs For example if you find that an application is short of memory alter the DRAM memory allocation from the System Properties window Caution Setting the Program Memory too low may prevent a...

Страница 51: ...a is displayed in the window The blue slider bar indicates the current amount of unallocated SDRAM and determines the boundaries within which the slider can move System Memory Slider Bar Note Storage memory is limited to a maximum of 128 MB Using the slider bar to increase storage memory will provide more RAM based storage in the folder Object Store 3 Tap OK to apply the new setting 4 Run the Back...

Страница 52: ...Notes 52 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 53: ...12 12 01 standard and CSA C22 2 No 213 M1987 Electromagnetic Compatibility Directive European Electromagnetic Compatibility EMC for Industrial Control Equipment Self declaration in accordance with European Directives EN61000 6 2 EN61000 6 4 Conditions of Safe Use for Installation in Hazardous Locations The following information applies to products bearing the UL marking for Hazardous areas for exp...

Страница 54: ...by GE Intelligent Platforms could void the user s authority to operate the equipment Industry Canada requires the following note to be published Note This Class A digital apparatus complies with Canadian CAN ICES 3 A NMB 3 A EMC Installation and Operation Considerations This equipment has been tested and found to comply with a minimum level of EMC performance as defined by EN 61000 6 2 and EN 6100...

Страница 55: ...uickPanel 10 Accessory Kit Replacement Mounting Clips Power and Serial Port Connectors IC755ACC10PRO QuickPanel 10 Replacement Screen Protectors Qty 3 IC755CSS12CDx QuickPanel 12 Color TFT with Multi touch Projected Capacitive Screen 12 24 V dc Powered IC755ACC12GAS QuickPanel 12 Replacement Gasket IC755ACC12MNT QuickPanel 12 Accessory Kit Replacement Mounting Clips Power and Serial Port Connector...

Страница 56: ...Notes 56 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 57: ...n the screw clamps The torque for the attaching screws is 0 3 Nm 2 66 in lb Interface x1 RS 232 x1 RS 232 485 default is RS 485 Connectors Euro Terminal Tyco Electronics 1 284539 0 Mating Connector Tyco Electronics 1 284510 0 Pin Signal Name Pin out COM1 10 1 1 TXD 2 RXD 3 RTS 4 CTS 5 SGND COM2 RS 232 485 6 TXD TXD DATA 7 RXD TXD DATA 8 RTS RXD DATA 9 CTS RXD DATA 10 SG RS 485 mode shorts pins 6 8...

Страница 58: ...Notes 58 GFK 2847F QuickPanel Operator Interface User Manual For public disclosure ...

Страница 59: ...llation 27 battery 34 guidelines 53 Installing panel mounting 29 protective sheet 27 IP Address 40 K Keyboard 49 external 49 SIP 49 L LED Operation status 14 M Machine Edition 22 updating a project 23 Memory 50 DRAM 50 Modifying allocation 51 Mounting VESA Arm 33 Mounting Angle 28 mounting location protective sheet 28 Mounting location 28 Mouse 49 N Network device name 19 O Operating Sytsem 21 P P...

Страница 60: ...el 49 Software 21 Specifications 7 environmental 9 general 7 physical and mounting 8 Startup 18 Status Indicators 14 Store Manager 21 T Touchscreen calibrating 48 display 47 U Universal Serial Bus USB Ports 44 Unpacking and Inspection 15 USB device port details 44 host port details 44 V VESA Arm mounting 33 60 QuickPanel Operator Interface User Manual For public disclosure ...

Страница 61: ......

Страница 62: ...GE Intelligent Platforms 1 800 433 2682 1 434 978 5100 www ge ip com GFK 2847F For public disclosure ...

Отзывы: