CHAPTER 5: SETPOINTS
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
5–47
is equalled or exceeded. Selecting “Aux1”, “Aux2”, or “Aux3” activates the respective
auxiliary relay with no message displayed. This is intended for process control.
•
PHASE A/B/C/NEUTRAL CURRENT DMD LEVEL
: When the phase A/B/C/ or neutral
current demand equals or exceeds this setpoint, a phase A/B/C or neutral demand
alarm or process control indication occurs.
•
3
Φ
POS/NEG REAL PWR DMD RELAY
: Three-phase positive/negative real power
demand detection can either be disabled or used as an alarm or process control. Set
this setpoint to “Off” if the feature is not required. Selecting “Alarm” activates the alarm
relay and displays an alarm message whenever the positive/negative three-phase
real power demand level is equalled or exceeded. Selecting “Aux1”, “Aux2”, or “Aux3”
activates the respective auxiliary relay with no message displayed. This is intended for
process control.
•
3
Φ
POS/NEG REAL PWR DMD LEVEL
: When the three-phase real power demand
exceeds this setpoint, a three-phase positive/negative real power demand alarm or
process control indication will occur.
•
3
Φ
POS/NEG REACT PWR DMD RELAY
: Three-phase positive/negative reactive power
demand detection can either be disabled or used as an alarm or process control. Set
to “Off” if this feature is not required. Selecting “Alarm” activates the alarm relay and
displays an alarm message whenever the positive/negative three-phase reactive
power demand level is equalled or exceeded. Selecting “Aux1”, “Aux2”, or “Aux3”
activates the respective auxiliary relay with no message displayed. This is intended for
process control.
•
3
Φ
POS/NEG REACT PWR DMD LEVEL
: When the three-phase reactive power demand
equals or exceeds this setpoint, a three-phase positive/negative reactive power
demand alarm or process control indication will occur.
•
3
Φ
APPARENT POWER DEMAND RELAY
: Three-phase apparent power demand
detection can be disabled or used as an alarm or process control. Set to “Off” if this
feature is not required. Selecting “Alarm” activates the alarm relay and displays an
alarm message if the three-phase apparent power demand level is equalled or
exceeded. Selecting “Aux1”, “Aux2”, or “Aux3” activates the respective auxiliary relay
with no message displayed. This is intended for process control.
•
3
Φ
APPARENT POWER DEMAND LEVEL
: When the three-phase apparent power
demand equals or exceeds this setpoint, a three-phase apparent power alarm or
process control indication will occur.
Содержание PQM II
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights ...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture ...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION ...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder ...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE ...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING ...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS ...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY ...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A ...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX ...